This paper presents a coordinated voltage control scheme (CVCS) for a cluster of offshore wind power plants connected to a voltage-source converter-based high-voltage direct current system. The primary control point of the proposed voltage control scheme is the introduced Pilot bus, which is having the highest short-circuit capacity in the offshore AC grid. The developed CVCS comprehends an optimization algorithm, aiming for minimum active power losses in the offshore grid, to generate voltage reference to the Pilot bus. During the steady-state operation, the Pilot bus voltage is controlled by dispatching reactive power references to each wind turbine (WT) in the wind power plant cluster based on their available reactive power margin and network sensitivity-based participation factors, which are derived from the dV/dQ sensitivity of a WT bus w.r.t. the Pilot bus. This method leads to the minimization of the risk of undesired effects, particularly overvoltage at the terminals of the WT located far away from the AC collector substation, by dispatching lower reactive power references compared with the ones nearer to the substation. In addition, this paper proposes a control strategy for improved voltage ride through capability of WTs for faults in the offshore grid, thus leading to improved dynamic voltage profile in the offshore AC grid.
22 September 2016 in IET Renewable Power Generation
A coordinated fast primary frequency control scheme from offshore wind power plants (OWPPs) integrated to a three terminal high voltage DC (HVDC) system is proposed in this study. The impact of wind speed variation on the OWPP active power output and thus on the AC grid frequency and DC grid voltage is analysed. The removal of active power support from OWPP after the frequency control action may result in second frequency (and DC voltage) dips. Three different methods to mitigate these secondary effects are proposed, such as, (i) Varying the droop gains of the HVDC converter (ii) Releasing the active power support from OWPP with a ramp rate limiter and (iii) An alternative method for the wind turbine overloading considering rotor speed. The effectiveness of the proposed control scheme is demonstrated on a wind power plant integrated into a three terminal HVDC system developed in DIgSILIENT PowerFactory. The results show that the proposed coordinated frequency control method performs effectively at different wind speeds and minimises the secondary effects on frequency and DC voltage.
In recent years, renewable energy sources have been integrated on a large scale in power systems all around the world to address the environmental sustainability concerns. With conventional thermal generators being phased out, large offshore wind power plants present a viable alternative to provide blackstart services for power system restoration. By means of simulations, grid‐forming wind turbines are shown to successfully energize the offshore transformer and the high‐voltage direct current (HVDC) export link in a controlled manner, to ultimately supply onshore block load. Two methods for energizing the offshore network have been compared: the prevalent hard‐switching approach and the more complex soft‐start method. Additionally, control has been implemented to mitigate the significant transients in the export link associated with pre‐charging of the onshore converter. It is shown that soft‐start can provide faster energization with smaller transients compared to hard‐switching. Moreover, the sensitivity analyses performed in this study illustrate the impact of pre‐insertion resistor and voltage ramp‐up rates on transients during hard‐switching and soft‐start, respectively. The results presented also show that grid‐forming wind power plants can deal with controlled pre‐charging of the onshore converter from its DC terminals that is essential for the safe energization and operation of the export link.
24 June 2020 in IEEE Transactions on Sustainable Energy
Before diode rectifier (DR) technology for connecting offshore wind farms (OWFs) to HVdc is deployed, in-depth studies are needed to assess the actual capabilities of DR-connected OWFs to contribute to the secure operation of the networks linked to them. This study assesses the capability of such an OWF to provide communication-less frequency support (CLFS) to an onshore ac network. It is shown that the HVdc link's offshore terminal direct voltage can be estimated from measurements at the OWF's point of connection with the DR platform. Two different methods are proposed for implementing CLFS in the OWF active power controls. In Method 1, the estimated offshore terminal direct voltage is used for estimating the onshore frequency deviation. In Method 2, the actual offshore terminal direct voltage measurement is used instead. Unique features of the provision of CLFS from OWFs connected to HVdc via DRs are highlighted, and the dynamic and static performance of the CLFS control scheme is compared to that of the communication-based frequency support scheme. To assess the impact of parameter estimation errors on the provision of CLFS, a parametric sensitivity study is presented as well, and recommendations are given to increase accuracy.
The current practice of power system restoration mainly relies on conventional power plants, which can provide black start in case of a black out using fossil fuels. HVdc-connected offshore wind power plants can, on the other hand, provide fast and environmentally friendly solutions for power system restoration, once their state of the art wind turbines are equipped with the grid-forming capability. In this paper, the background and existing solutions for wind turbine and wind power plant self-energization and onshore grid black start are presented, together with simulation results of an offshore wind power plant sequentially energizing the offshore ac network, offshore HVdc terminal, HVdc link, onshore HVdc terminal, and onshore ac terminal and load.
This paper is focused on the design of a controller for the DC/DC boost converter using K factor control, which is based on modified PI control method, for maximum power point tracking (MPPT) of solar PV system. A mathematical model for boost converter based on small signal averaging approach is presented. Design of the passive elements of the boost converter as per the system specifications is also illustrated. The performance of the proposed K factor control method is verified with the simulations for MPPT on solar PV system at different atmospheric conditions. A new circuit based model for solar PV array, which includes the effect of solar insolation and temperature on PV array output, for the application in power system transient simulations, is also presented. The performance of the PV array model is verified with simulations at different atmospheric conditions. A 160W PV module from BP solar is modelled and its characteristics are validated with the corresponding results from its datasheet. The simulations are performed using PSCAD/EMTDC.