The theme of this paper is three-phase distribution system modeling suitable for the Z-Bus load-flow. Detailed models of wye and delta constant-power, constant-current, and constant-impedance loads are presented. Models of transmission lines, step-voltage regulators, and transformers that build the bus admittance matrix (Y-Bus) are laid out. The Z-Bus load-flow is then reviewed and the singularity of the Y-Bus in case of certain transformer connections is rigorously discussed. Based on realistic assumptions and conventional modifications, the invertibility of the Y-Bus is proved. Last but not least, MATLAB scripts that model the components of the IEEE 37-bus, the IEEE 123-bus, the 8500-node feeders, and the European 906-bus low-voltage feeder are provided.
3 February 2016 in IEEE Transactions on Smart Grid
This paper develops a power management scheme that jointly optimizes the real power consumption of programmable loads and reactive power outputs of photovoltaic (PV) inverters in distribution networks. The premise is to determine the optimal demand response schedule that accounts for the stochastic availability of solar power, as well as to control the reactive power generation or consumption of PV inverters adaptively to the real power injections of all PV units. These uncertain real power injections by PV units are modeled as random variables taking values from a finite number of possible scenarios. Through the use of second order cone relaxation of the power flow equations, a convex stochastic program is formulated. The objectives are to minimize the negative user utility, cost of power provision, and thermal losses, while constraining voltages to remain within specified levels. To find the global optimum point, a decentralized algorithm is developed via the alternating direction method of multipliers that results in closed-form updates per node and per scenario, rendering it suitable to implement in distribution networks with a large number of scenarios. Numerical tests and comparisons with an alternative deterministic approach are provided for typical residential distribution networks that confirm the efficiency of the algorithm.
This paper derives a set of sufficient conditions guaranteeing that the load-flow problem in unbalanced three-phase distribution networks with wye and delta constant-power, constant-current, and constant-impedance loads (ZIP loads) has a unique solution over a region that can be explicitly calculated from the network parameters. It is also proved that the well-known Z-Bus iterative method is a contraction over the defined region, and hence converges to the unique solution.
20 September 2018 in IEEE Transactions on Power Systems
This paper develops a tractable formulation for optimal placement and sizing of inverter-based renewable systems in multi-phase distribution networks. The goal of the formulation is to minimize the cost of inverter installation, average power import, and average distributed generation curtailment. Threephase and single-phase inverter models are presented that preserve the underlying mappings between renewable uncertainty to power injection. The uncertainty of distributed generators (DGs) and loads are characterized by a finite set of scenarios. Linear multi-phase power flow approximations are used in conjunction with scenario reduction techniques to arrive at a tractable twostage stochastic formulation for optimal DG placement and sizing. First-stage decisions are locations for DG deployment and capacity sizes, and second-stage decisions include DG real power curtailment, reactive power support, as well as feeder voltage profile. The resulting formulation is a mixed-integer second-order cone program and can be solved efficiently either by existing optimization solvers or by relaxing the binary variables to the [0,1] interval. Simulation studies on standard multi-phase IEEE test feeders promise that optimal stochastic planning of DGs reduces costs during validation, compared to a scheme where uncertainty is only represented by its average value.
This paper develops a branch-flow based optimal power flow (OPF) problem for multi-phase distribution networks that allows for tap selection of wye, closed-delta, and open-delta step-voltage regulators (SVRs). SVRs are assumed ideal and their taps are represented by continuous decision variables. To tackle the non-linearity, the branch-flow semidefinite programming framework of traditional OPF is expanded to accommodate SVR edges. Three types of non-convexity are addressed: (a) rank-1 constraints on non-SVR edges, (b) nonlinear equality constraints on SVR power flows and taps, and (c) trilinear equalities on SVR voltages and taps. Leveraging a practical phase-separation assumption on the SVR secondary voltage, novel McCormick relaxations are provided for (c) and certain rank-1 constraints of (a), while dropping the rest. A linear relaxation based on conservation of power is used in place of (b). Numerical simulations on standard distribution test feeders corroborate the merits of the proposed convex formulation.
23 July 2019 in IEEE Transactions on Control of Network Systems
Uncertainty from renewable energy and loads is one of the major challenges for stable grid operation. Various approaches have been explored to remedy these uncertainties. In this paper, we design centralized or decentralized state-feedback controllers for generators while considering worst-case uncertainty. Specifically, this paper introduces the notion of $\mathcal{L}_{\infty}$ robust control and stability for uncertain power networks. Uncertain and nonlinear differential algebraic equation model of the network is presented. The model includes unknown disturbances from renewables and loads. Given an operating point, the linearized state-space presentation is given. Then, the notion of $\mathcal{L}_{\infty}$ robust control and stability is discussed, resulting in a nonconvex optimization routine that yields a state feedback gain mitigating the impact of disturbances. The developed routine includes explicit input-bound constraints on generators' inputs and a measure of the worst-case disturbance. The feedback control architecture can be centralized, distributed, or decentralized. Algorithms based on successive convex approximations are then given to address the nonconvexity.