In this paper, the solid desiccant adsorption packed bed with a three-stage internal cooling (ICSPB) has been proposed to improve the dehumidification efficiency and make a comparison with that of non-internal cooling. To investigate the performance of the ICSPB, the dehumidification capacity, dehumidification efficiency, water content of solid desiccant, moisture ratio of solid desiccant, temperature of solid desiccant and inlet and outlet air temperature difference were discussed in different conditions of inlet air and supplying water temperature. It was found that the dehumidification performance of the bed with internal cooling could be improved greatly in the low temperature and low humidity conditions, while in the high temperature and humid, the improvement was not obvious. With internal cooling, the dehumidification efficiency and the water content of the solid desiccant could be improved 59.69% and 110.7%, respectively, and the temperature of solid desiccant could be reduced 2.2 °C when the ICSPB operated at the inlet air temperature of 20 °C, inlet humidity of 55%, and water temperature of 14 °C. Moreover, the dehumidification performance at each stage of ICSPB was studied. It was found that, the first stage played the most important role in the dehumidification process. In addition, the calculation models that can be used to predict the moisture ratio and the temperature of solid desiccant were established on the test results.
In this paper, a rear door oil-cooling heat exchanger for data center cabinet-level cooling has been proposed. In order to solve the heat dissipation problem of high heat density data center, this paper applied the mature transformer oil cooling technology to the data room. The heat dissipation of liquid-cooled cabinets and traditional air-cooled cabinets was compared, and the heat dissipation performance of the oil-cooled system was theoretically and experimentally investigated. To investigate the heat dissipation system, the cabinet operating temperature, circulating oil system temperature and cabinet exhaust temperature, cabinet heat density, oil flow rates and fan power were analyzed. It was found that the average cooling efficiency of the liquid-cooled cabinet increased by 66% compared with the average cooling efficiency of the conventional air-cooled cabinet. The operating temperature in air-cooled cabinets is as high as 55 °C, and the operating temperature in liquid-cooled cabinets does not exceed 50 °C. Among which, the maximum heat dissipation efficiency of the liquid-cooled cabinets can reach 58.8%. The oil temperature could reach 46.9 °C after heat exchange, and the exhaust air of the cabinet could reach 42.8 °C, which could be used to prepare domestic water and regenerative desiccant. The results from established calculation model agreed well with the testing results and the model could be used to predict the heat dissipation law of the oil cooling system under different conditions. The research has proposed the potential application of the oil-cooled in cabinet-level cooling, which can help realize saving primary energy and reducing carbon emission.