With the rapid development of ultra-high-voltage (UHV) AC/DC, especially the step-by-step upgrading of the UHV DC transmission scale, security presents new challenges. Commutation failure (CF) is a common fault in line commutated converter (LCC) high-voltage direct current (HVDC) power systems. Once failure happens, it may cause power oscillations in a system. In this paper, taking a two-area AC/DC parallel interconnected power system as the example, based on the impulse response model of second-order linear system, the mechanism of power oscillation on the AC tie-line caused by CF are clarified. It is proved that the peak value of the AC tie-line power oscillation is mainly determined by the DC power and the equivalent CF duration, the frequency and damping ratio of dominant area oscillation mode. Meanwhile, the peak time is mainly determined by the oscillation frequency. Finally, the correctness and effectiveness of the algorithms are verified by a simulation analysis of an extended IEEE-39-bus AC/DC parallel interconnected power system. These research results can provide a basis for the arrangement of the operating modes and the formulation of control measures for interconnected power grids.
To solve the problems of large switching losses and the need for large-capacity electrolytic capacitances in three-phase DC/AC on-board chargers for vehicle-to-grid (V2G) applications, this paper proposes a single-stage bidirectional high-frequency isolated converter that eliminates the need for large-capacity capacitances. Combined with the proposed modulation scheme, it can theoretically reduce the switching loss by about two-thirds with the three-phase converter compared with the conventional modulation scheme, improving the converter’s operating efficiency and power density. Firstly, based on the characteristics of the proposed topology, a hybrid modulation scheme is proposed, which combines a phase-shift modulation scheme based on double modulation waves and a sawtooth carrier with a 1/3 modulation scheme, and the theoretical feasibility of the hybrid modulation scheme is verified using a mathematical modeling equation. Secondly, this paper provides a detailed analysis of the four operating modes of the two full-bridge circuits and the commutation process of the three-phase converter within 1/6 of the fundamental frequency cycle (P1 modulation interval). Then, the control strategy is given for the constant-current and constant-voltage charging and constant-current discharging for electric vehicle batteries. Finally, simulation results verify the correctness of the proposed topology and modulation scheme in vehicle–grid interaction.