Accurate and reliable lightning current data are the basis of lightning protection design. To measure lightning current data at different measurement locations in a transmission system, the limitations of traditional lightning current sensors are analyzed, and optical current sensing technology is adopted, which has the advantages of no magnetic saturation and no bandwidth limitation. Compared with traditional application environments, the sensing technology is used in special environments in transmission systems. This paper analyzes the influence of environmental factors on sensors, and combines the extreme environmental requirements, such as temperature and insulation requirements, to study the sensor. Starting from the sensitivity, the sensing characteristics of the sensor are analyzed. The sensor is designed according to three aspects: sensing material selection, spatial measuring position, and sensing material size optimization, such that it can satisfy the different measurement requirements of towers, overhead ground wires, and transmission lines, respectively. The experiments indicate that the developed sensors can meet the measurement sensitivity requirements of different types of lightning strikes. The experimental results of sensors exhibit a reasonable amplitude measurement accuracy, linearity, and waveform measurement capability. These results provide important theoretical and experimental bases for the application of optical current sensing technology to the measurement of the lightning current of transmission systems.
The operational reliability directly affects the practical application of optical current transformers (OCTs) in smart substations. As the key component of the OCT, the reliability of the optical current sensor (OCS) largely determines the reliability level of the OCT. This paper proposes a reliability assessment method of the OCS based on accelerated aging tests. The failure modes and failure mechanisms of the OCS are analyzed, and the concept of OCS insertion loss variation is proposed. An allowable range of insertion loss variation is selected as the failure criterion of the OCS. From the viewpoint of the OCS measurement error generated by the quantization error of the analog-to-digital converter, the allowable range of insertion loss variation is obtained. By selecting a high temperature as the accelerated thermal stress, we design the accelerated aging test scheme of the OCS and analyze the sample test data to obtain the activation energy of the OCS insertion loss failure. Based on this activation energy, the median time to failure and instantaneous failure rate curve of the OCS at normal temperature are obtained. The results indicate that the designed OCS has an expected service life of 50 years and a low instantaneous failure rate at normal temperature. This paper provides basic critical reliability analysis data for the system reliability assessment of OCTs.
When applying an optical current transformer (OCT) to direct current measurement, output signals exhibit a low signal-to-noise ratio and signal-to-noise band overlap. Sinusoidal wave modulation is used to solve this problem. A double correlation detection algorithm is used to extract the direct current (DC) signal, remove white noise and improve the signal-to-noise ratio. Our sensing unit uses a terbium gallium garnet crystal in order to increase the output signal-to-noise ratio and measurement sensitivity. Measurement errors of single correlation and double correlation detection algorithms are compared, and experimental results showed that this measurement method can control measurement error to about 0.3%, thus verifying its feasibility.