The adaptation of dielectric windows as metamaterial superstrate over a bio-inspired Printed Monopole Antenna (PMA) was evaluated in order to improve the detection sensitivity of Ultra High Frequency (UHF) sensors designed for Partial Discharge (PD) measurement. For this purpose, rectangular and circular Split Ring Resonators (SRR) structures were designed and evaluated aiming to achieve a metamaterial superstrate that improves the characteristics of the bio-inspired PMA as the gain, bandwidth, and radiation pattern. Measurements of the PMA with metamaterial superstrate were carried out in an anechoic chamber and compared to the simulations performed. The results show that the metamaterial superstrate insertion did not impact the original operating bandwidth, covering most of the characteristic frequency range of PD activity. Moreover, this insertion resulted in a mean gain enhancement of 0.7 dBi regarding the reference PMA, resulting in an antenna with better sensitivity for PD detection (mean gain of 3.61 dBi). The PMA-metamaterial set PD detection sensitivity was evaluated through laboratory tests with a point-to-plane PD generator setup and in field with measurements from a 230 kV current transformer. The developed PMA-metamaterial set was able to detect, successfully, the activity of PD for both tests, being classified as an optimized sensor for PD detection through dielectric windows.
In this paper, the practical application of a bio-inspired antenna for partial discharge (PD) detection in high voltage equipment was evaluated in order to validate the efficiency of using this technology for PD monitoring purposes. For this, PD measurements using the bio-inspired antenna were performed on operational 69 kV potential transformers (PT) in a real substation. After the field experiment, laboratory measurements using the IEC 60270 standard method and a bio-inspired antenna were performed, simultaneously, over the evaluated PT. The results obtained at the substation indicated suspicious frequencies of partial discharge activity in two out of three evaluated potential transformers, mainly for the frequencies of 461 MHz, 1366 MHz, 1550 MHz and 1960 MHz. During the laboratory tests, the presence of partial discharge activity over the suspicious potential transformers was confirmed with the detection of PD apparent charge levels above 20 pC. Finally, the frequency spectrum obtained from the PD signals detected by the bio-inspired antenna in the laboratory presented similar frequency values to those obtained during the practical application at the substation, making it a promising indicator for future defect classification studies using artificial intelligence.