12 December 2019 in IEEE Journal of Emerging and Selected Topics in Power Electronics
Verified
Journal Article
Closed access
TQTaoufik Qoria
Taoufik Qoria
FGFrancois Gruson
Francois Gruson
FCFrederic Colas
Frederic Colas
GDGuillaume Denis
Guillaume Denis
TPThibault Prevost
Thibault Prevost
XGXavier Guillaud
Xavier Guillaud
The present paper deals with the post-fault synchronization of a voltage source converter based on the droop control. In case of large disturbances on the grid, the current is limited via current limitation algorithms such as the virtual impedance. During the fault, the power converter internal frequency deviates resulting in a converter angle divergence. Thereby, the system may lose the synchronism after fault clearing and which may lead to instability. Hence, this paper proposes a theoretical approach to explain the dynamic behavior of the grid forming converter subject to a three phase bolted fault. A literal expression of the critical clearing time is defined. Due to the precise analysis of the phenomenon, a simple algorithm can be derived to enhance the transient stability. It is based on adaptive gain included in the droop control. These objectives have been achieved with no external information and without switching from one control to the other. To prove the effectiveness of the developed control, experimental test cases have been performed in different faulted conditions.

1 June 2018
Verified
Conference Paper
Closed access
TQT. Qoria
T. Qoria
FGFrancois Gruson
Francois Gruson
FCF. Colas
F. Colas
XGX. Guillaud
X. Guillaud
MDM-S. Debry
M-S. Debry
TPT. Prevost
T. Prevost

11 July 2017 in IEEE Transactions on Power Delivery
Verified
Journal Article
Closed access
JFJulian Freytes
Julian Freytes
GBGilbert Bergna
Gilbert Bergna
JSJon Are Suul
Jon Are Suul
SDSalvatore D'ARco
Salvatore D'ARco
FGFrancois Gruson
Francois Gruson
XGXavier Guillaud
Xavier Guillaud
The dc-side dynamics of modular multilevel converters (MMCs) can be prone to poorly damped oscillations or stability problems when the second-harmonic components of the arm currents are mitigated by a circulating current suppression controller (CCSC). This paper demonstrates that the source of these oscillations is the uncontrolled interaction of the dc-side current and the internally stored energy of the MMC, as resulting from the CCSC. Stable operation and improved performance of the MMC control system can be ensured by introducing the closed-loop control of the energy and the dc-side current. The presented analysis relies on a detailed state-space model of the MMC, which is formulated to obtain constant variables in steady state. The resulting state-space equations can be linearized to achieve a linear time invariant model, allowing for eigenvalue analysis of the small-signal dynamics of the MMC. Participation factor analysis is utilized to identify the source of the poorly damped dc-side oscillations, and indicates the suitability of introducing control of the internal capacitor voltage or the corresponding stored energy. An MMC connected to a dc power source with an equivalent capacitance, and operated with dc voltage droop in the active power flow control, is used as an example for the presented analysis. The developed small-signal models and the improvement in small-signal dynamics achieved by introducing control of the internally stored energy are verified by time-domain simulations in comparison to an electro-magnetic transient (EMT) simulation model of an MMC with 400 submodules per arm.

5 September 2018 in IEEE Transactions on Power Delivery
Verified
Journal Article
Closed access
JFJulian Freytes
Julian Freytes
SASamy Akkari
Samy Akkari
PRPierre Rault
Pierre Rault
MBMohamed Moez Belhaouane
Mohamed Moez Belhaouane
FGFrancois Gruson
Francois Gruson
XGXavier Guillaud
Xavier Guillaud
This article deals with DC voltage dynamics of Multi-Terminal HVDC grids with energy-based controlled Mo\-dular Multilevel Converters (MMC) adopting the commonly used power-voltage droop control technique for power flow dispatch. Special focus is given on the energy management strategies of the MMCs and their ability to influence on the DC voltage dynamics. First, it is shown that decoupling the MMC energy from the DC side by controlling the energy to a fixed value, regardless of the DC voltage level, causes large and undesired DC voltage transient after a sudden power flow change. Second, the Virtual Capacitor Control technique is implemented in order to improve the results, however, its limitations on droop-based MTDC grids are highlighted. Finally, a novel energy management approach is proposed to improve the performance of the later method. These studies are performed with detailed MMC models suitable for the use of linear analysis techniques. The derived MTDC models are validated against time-domain simulations using detailed EMT MMC models with 400 sub-modules per arm.

9 September 2009 in IEEE Transactions on Power Electronics
Verified
Journal Article
Closed access
PGPetar J. Grbovic
Petar J. Grbovic
FGFrancois Gruson
Francois Gruson
NINadir Idir
Nadir Idir
PMPhilippe Le Moigne
Philippe Le Moigne
Turn-on performance of a reverse blocking insulated gate bipolar transistor (RB IGBT) is discussed in this paper. The RB IGBT is a specially designed IGBT having ability to sustain blocking voltage of both the polarities. Such a switch shows superior conduction but much worst switching (turn- on) performances compared to a combination of an ordinary IGBT and blocking diode. Because of that, optimization of the switching performance is a key issue that makes the RB IGB not well accepted in the real applications. In this paper, the RB IGBT turn-on losses and reverse recovery current are analyzed for different gate driver techniques, and a new gate driver is proposed. Commonly used conventional gate drivers do not have capability for the switching dynamics optimization. In contrast to this, the new proposed gate driver provides robust and simple way to control and optimize the reverse recovery current and turn-on losses. The collector current slope and reverse recovery current are controlled by the means of the gate emitter voltage control in feedforward manner. In addition, the collector emitter voltage slope is controlled during the voltage falling phase by the means of inherent increase of the gate current. Therefore, the collector emitter voltage tail and the total turn- on losses are reduced, independently on the reverse recovery current. The proposed gate driver was experimentally verified and the results presented and discussed.

27 April 2018 in IEEE Transactions on Sustainable Energy
Verified
Journal Article
Closed access
HZHaibo Zhang
Haibo Zhang
FGFrancois Gruson
Francois Gruson
DFDiana FLOREZ
Diana FLOREZ
CSChristophe Saudemont
Christophe Saudemont
This paper describes the characteristics of a series parallel wind farm (SPWF) topology and investigates the control strategy to ensure its safe operation. The SPWF was found to have advantages over other pure dc wind farm architectures in terms of lower construction cost and lower power losses in the collection system. However, unbalance power productions among the wind turbines cause the variations of their output voltages, which may endanger the safe operation of the entire wind farm. This paper proposes a global control strategy that prevents wind turbines from operating above their overvoltage capabilities. With an active participation of the onshore converter, the proposed strategy allows maximum power point tracking (MPPT) of the wind turbines. The practical limitations of this strategy are discussed and improvements are given. The feasibility of the proposed method is validated in a simulation of 300 MW wind farm developed in EMTP-RV.