In this paper, a fault-tolerant control scheme is proposed for the rigid spacecraft attitude control system subject to external disturbances, multiple system uncertainties, and actuator faults. The angular velocity measurement is unavailable, which increases the complexity of the problem. An observer is first designed based on the super-twisting sliding mode method, which can provide accurate estimates of the angular velocity in finite time. Then, an adaptive fault-tolerant controller is proposed based on neural networks using the information from the observer. It is shown that the attitude orientations converge to the desired values exponentially. Finally, a simulation example is utilized to verify the effectiveness of the proposed scheme.
13 December 2018 in IEEE Transactions on Industrial Electronics
Alarm systems play critically important roles for the safe and efficient operation of industrial plants, but they often suffer from too many nuisance alarms. Deadbands are widely used in industrial alarm systems to reduce the number of nuisance alarms. This paper formulates an index to determine whether deadbands are suitable for removing nuisance alarms of an analog signal, and proposes a method to design the deadband width. First, the deadband index is defined from two metrics, namely, normalized alarm durations and normalized alarm deviations. If the index is larger than $45^{\circ}$ , as indicated by a hypothesis test, then nuisance alarms are associated with large/small normalized alarm durations/deviations, so that deadbands are suitable. Second, a design method is proposed to find an optimal deadband width, so as to achieve the best weighted balance between the time duration of nuisance alarms and the delay in detecting abnormal conditions. The proposed method is applicable to non-IID (independent and identically distributed) signals, whereas available design methods are confined to IID signals. Industrial examples are provided to validate the deadband index and the design method.
28 August 2019 in IEEE Transactions on Automation Science and Engineering
A new method is proposed to predict upcoming alarm events for a current alarm sequence by exploiting similar historical alarm flood sequences. The proposed method is composed of two main steps. The first step sorts the historical alarm flood sequences in the descending order of similarity scores with respect to the current alarm sequence. The second step chooses some subsequence of recent alarm events in the current alarm sequence and predicts an upcoming alarm event based on these similar historical alarm flood sequences having the same subsequence. A Bayesian estimator is exploited to calculate the posterior probabilities and their confidence intervals for all the candidates of predicted alarm events. The optimal predicted alarm event is the one with the largest lower bound of posterior probability as a quantitative measurement of prediction reliabilities. The proposed method resolves a dilemma between a long (short) subsequence of the current alarm sequence and a small (large) number of the same subsequences in the historical alarm flood sequences. Numerical examples are provided to support the proposed method.
13 March 2019 in IEEE Transactions on Industrial Electronics
Alarm systems are critically important for safety and efficiency of industrial plants. However, many alarm variables in contemporary alarm systems are generated in a way being isolated from related process variables, resulting in false and missing alarms. This paper is motivated by abnormality detection for condensate-water electrical pumps in thermal power plants and proposes a method to design multivariate alarm systems for time-varying processes. A novel feature to distinguish normal and abnormal conditions is observed on the variation rates of multiple linear regression model parameters. A model estimator based on Bayesian filters is formulated to track the variations of model parameters in normal conditions, and not to do so in abnormal conditions so that absolute cumulative modeling errors are large enough to raise alarms. The effectiveness of the proposed method is validated by industrial case studies.