Alarm systems are critically important for safety and efficiency of industrial plants. However, many alarm variables in contemporary alarm systems are generated in a way being isolated from related process variables, resulting in false and missing alarms. This paper is motivated by abnormality detection for condensate-water electrical pumps in thermal power plants and proposes a method to design multivariate alarm systems for time-varying processes. A novel feature to distinguish normal and abnormal conditions is observed on the variation rates of multiple linear regression model parameters. A model estimator based on Bayesian filters is formulated to track the variations of model parameters in normal conditions, and not to do so in abnormal conditions so that absolute cumulative modeling errors are large enough to raise alarms. The effectiveness of the proposed method is validated by industrial case studies.
This paper proposes a parallel grid search algorithm to find an optimal operating point for minimizing the power consumption of an experimental heating, ventilating and air conditioning (HVAC) system. First, a multidimensional, nonlinear and non-convex optimization problem subject to constraints is formulated based on a semi-physical model of the experimental HVAC system. Second, the optimization problem is parallelized based on Graphics Processing Units to simultaneously compute optimization loss functions for different solutions in a searching grid, and to find the optimal solution as the one having the minimum loss function. The proposed algorithm has an advantage that the optimal solution is known with evidence as to the best one subject to current resolutions of the searching grid. Experimental studies are provided to support the proposed algorithm.