Junghyon Mun

Dr. Junghyon Mun

Sun&Light
orcid

Research Focus & Metrics

Academic Career Length

6Years (2021-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
4 January 2023 in Sensors
Verified
Journal Article
Open access
PDF file
JKJehyun Kim
Jehyun Kim
JBJONG IL BANG
JONG IL BANG
ACAnseop Choi
Anseop Choi
JMJunghyon Mun
Junghyon Mun
MSMinki Sung
Minki Sung
Infectious diseases such as the COVID-19 pandemic have necessitated preventive measures against the spread of indoor infections. There has been increasing interest in indoor air quality (IAQ) management. Air quality can be managed simply by alleviating the source of infection or pollution, but the person within a space can be the source of infection or pollution, thus necessitating an estimation of the exact number of people occupying the space. Generally, management plans for mitigating the spread of infections and maintaining the IAQ, such as ventilation, are based on the number of people occupying the space. In this study, carbon dioxide (CO2)-based machine learning was used to estimate the number of people occupying a space. For machine learning, the CO2 concentration, ventilation system operation status, and indoor–outdoor and indoor–corridor differential pressure data were used. In the random forest (RF) and artificial neural network (ANN) models, where the CO2 concentration and ventilation system operation modes were input, the accuracy was highest at 0.9102 and 0.9180, respectively. When the CO2 concentration and differential pressure data were included, the accuracy was lowest at 0.8916 and 0.8936, respectively. Future differential pressure data will be associated with the change in the CO2 concentration to increase the accuracy of occupancy estimation.

1 July 2021 in Energies
Verified
Journal Article
Open access
PDF file
YAYonghan Ahn
Yonghan Ahn
HJHan-byeol Jang
Han-byeol Jang
JMJunghyon Mun
Junghyon Mun
The purpose of this study is to compare the load calculation results by a model using the air changes per hour (ACH) method and a model using an airflow network (AFN) and to ascertain what causes the difference between the two models. In the basic case study, the difference in the heat transfer distribution of the model in the interior space was investigated. The most significant difference between the two models is the heat transfer that results from infiltration. Parameter analysis was performed to investigate the relationship between the difference and the environmental variables. The result shows that the greater the difference is between the air temperature inside the balcony and the outdoor air temperature, and the greater the air flows from the balcony to the residential area, and the greater the heating and cooling load difference occurs. The analysis using the actual weather files of five domestic cities in South Korea rather than a virtual case shows that the differences are not so obvious when the wind blows at a constant speed throughout the year, but are dominant when the wind does not blow during the night and is stronger alongside the occurrence of sunlight during the day.