In this study, full-scale fire tests and finite element (FE) analyses are conducted to investigate the fire resistance performance of hollow-core slabs (HCSs) manufactured using the extrusion method. The deflection of the HCS specimens and the temperature distribution in the section according to the fire exposure time are measured and analyzed comprehensively, and the test results are compared with the FE analysis results. In addition, parametric analyses are conducted on 21 cases with the HCS depth, span length, hollow ratio in a section, cover thickness of concrete, and load ratio (i.e., the ratio of the external load to the ultimate load) as variables, based on which the fire resistance performance of the HCS according to each variable is investigated. The analysis results show that the load ratio is a key factor governing the fire resistance behavior of HCSs, whereas the effects of the cover thickness of concrete and the hollow ratio in a section are relatively slight within the range of variables examined in this study.
When fire occurs in a large multiplex building, the direction of smoke and flames is often similar to that of the evacuation of building occupants. This causes evacuation bottlenecks in a specific compartment, especially when the occupant density is very high, which unfortunately often leads to many fatalities and injuries. Thus, the development of an egress model that can ensure the safe evacuation of occupants is required to minimize the number of casualties. In this study, the correlations between fire temperature with visibility and toxic gas concentration were investigated through a fire simulation on a multiplex building, from which databases for training of artificial neural networks (ANN) were created. Based on this, an ANN model that can predict the available safe egress time was developed, and it estimated the available safe egress time (ASET) very accurately. In addition, an egress model that can guide rapid and safe evacuation routes for occupants was proposed, and the rationality of the proposed model was verified in detail through an application example. The proposed model provided the optimal evacuation route with the longest margin of safety in consideration of both ASET and the movement time of occupants under fire.
Nursing hospitals have a high probability of casualties during a fire disaster because they have many patients with impaired mobility. In this study, fire and egress simulations were conducted to evaluate the egress safety of a typical nursing hospital. The available safe egress time (ASET) of the prototype nursing hospital was calculated using Fire Dynamics Simulator, and the required safe egress time (RSET) was estimated by Pathfinder, reflecting characteristics of the occupants. The egress safety of the nursing hospital was then evaluated by comparing the ASET and RSET, considering the number of egress guides and delay time. According to the simulation results, the RSET increased as the egress delay time increased and the number of egress guides decreased. In addition, it is estimated that at least 20 workers (egress guides) should be on duty in the prototype nursing hospital, even during shiftwork and night duty. Based on the simulation results, egress safety criteria have been proposed in terms of normalized numbers of egress guides and egress delay time. The proposed criteria can be very easily applied to evaluate the egress safety of a typical nursing hospital in operation.
This study aimed to evaluate the egress safety in nursing hospitals based on the capacity of the smoke exhaust system. To this end, the available safe egress time was calculated by analyzing changes in visibility, carbon monoxide, carbon dioxide, oxygen contents, and temperature depending on the fire duration. In addition, an egress simulation was performed using the number of workers (egress guides) and egress delay time as variables, and the required safe egress time was estimated. Based on the results, the egress safety of a prototype nursing hospital was evaluated. In this study, egress safety criteria to evaluate egress safety in a typical nursing hospital were presented, which are expressed in terms of normalized egress guides, the capacity ratio of the smoke exhaust system, and egress delay time. The proposed criteria can be used to evaluate the egress safety of typical nursing hospitals and to prepare complementary measures.
In recent years, the number of studio residential buildings has increased significantly in Korea, as well as in many other countries, due to changes in living patterns. In Korea especially, there have been many fire accidents in studio residential buildings, which have caused a huge number of casualties and property damages, because the buildings were not adequately equipped for firefighting. In this study, the egress safety of a typical studio residential building in Korea is analyzed. Fire simulations were performed with variables of the fire location and the capacity of the smoke exhaust system to estimate the available safe egress time (ASET); egress simulations were also performed with the variable of egress delay time, and the required safe egress time (RSET) was determined. Then, the egress safety was evaluated, and the criteria for egress safety evaluation were proposed based on the simulation results. A studio residential building with a floor plan different from the prototype was used to validate the proposed egress safety criteria. Finally, a simple evaluation model is presented to estimate the required safe egress time (RSET) without simulation and to examine the impact of bottlenecks.
About Me
Ph.D. student at Department of Architectural Engineering and Smart City Interdisciplinary Major Program, University of Seoul
Ph.D. student at Department of Architectural Engineering and Smart City Interdisciplinary Major Program, University of Seoul