30 April 2013 in IEEE Transactions on Power Delivery
A capacitor sensor with a high-voltage electrode inside the GIS tank has the best bandwidth among the sensors developed to measure the very fast transient overvoltage (VFTO). However, the low-voltage arm of the current measurement system is usually a handmade film capacitor which has disadvantages of unassigned capacitance value, temperature effect, and short lifespan. With a novel lower voltage arm based on surface-mounted devices, a wide-bandwidth, stable, and easy maintenance measuring system is proposed in this paper. It is found that the slight inherent inductance in the ground trace of the printed-circuit board can induce unexpected oscillations, which are demonstrated with theoretical analysis and experimental study. With the reforming of the printed-circuit board layout, the oscillation is reduced and 200-MHz high-frequency cutoff frequency is achieved. The environment experiment shows that the temperature effect on the developed sensor is much smaller than that on the conventional sensor. The VFTO generated by disconnector operation in 1100-kV GIS is measured by the developed system and a conventional broadband capacitor sensor. The contrastive results prove that the characteristic of the measuring system can meet the requirement of VFTO measurements. Thousands of measurements on ultra-high voltage GIS indicate that the developed measuring system is stable, and characteristics of the VFTO are gained.
25 October 2017 in Journal of Physics D: Applied Physics
Surface charge accumulation can incur changes in electric field distribution, involved in the electron propagation process, and result in a significant decrease in the surface flashover voltage. The existing 2D surface charge measurement fails to meet the actual needs in real engineering applications that usually adopt the 45° conical frustum insulators. The present research developed a novel 3D measurement platform to capture surface charge distribution on solid insulation under nanosecond pulse in a vacuum. The results indicate that all surface charges are positive under a positive pulse and negative under a negative pulse. Surface charges tend to accumulate more near the upper electrode. Surface charge density increases significantly with the increase in pulse counts and amplitudes. Accumulation of surface charge results in a certain decrease of flashover voltage. Taking consideration of the secondary electron emission for the surface charge accumulation, four materials were obtained to demonstrate the effects on surface charge. Combining the effect incurred by secondary electron emission and the weighty action taken by surface charge accumulation on the flashover phenomena, the discharge mechanism along the insulator surface under nanosecond pulse voltage was proposed.