A gain scheduled adaptive control scheme based on a polytopic linear parameter varying (LPV) system is proposed in this paper to damp sub-synchronous oscillations (SSOs) for power system integrated with permanent magnet synchronous generators (PMSGs) and operating under high wind speed variability. Firstly, the linearized state space model of the PMSG-integrated power system is established. Secondly, a polytopic LPV system is developed to account for the stochastic drift behavior and wind speed variability. Next, a gap metric-based nonlinearity measurement method is used for configuring the vertices of the polytope. The adaptive polytopic LPV controller is solved using linear matrix inequality and gain scheduling control theory, while mode identification based on a sliding window fast Fourier transform is employed for adaptively adjusting the polytopic LPV controller. Finally, the proposed polytopic LPV adaptive control scheme is compared with three other control techniques to demonstrate its effectiveness in suppressing SSOs.
20 January 2021 in Electric Power Components and Systems
The load angle of a synchronous generator connected to a power grid has an eigenfrequency that depends on the operating conditions. The existence of an eigenfrequency can make the generator sensitive to electrical and mechanical disturbances and motivates the use of damper windings and power stabilizing systems. Another reason for keeping load angle oscillations small is that they increase the eddy current losses in the stator core and clamping structure due to axial leakage flux. This is shown with transient finite element analyses and can be explained by a loss model derived from a phasor model of the eddy current loss density.