30 January 2019 in IEEE Transactions on Power Delivery
Induced losses are a significant part of the total losses generated in HVAC cables. Presently, IEC 60287-1-1 is used to calculate the ratio of induced loss in a cable's metal sheath to its conductor loss (λ1), assuming uniform current density in both conductors and sheaths. Although this assumption is reasonable for smaller cables, it is questionable for larger cables in close proximity, such as three-core (3C) export cables in Offshore Wind Farm (OWF) projects. The effects of this non-uniform current density cannot be easily treated via a straightforward, purely analytical approach, since conductor currents are not effectively represented by linear ones in larger cables, while sheath currents are also unevenly distributed. The present study employs 2-D Finite Element (FE) models to evaluate how accurate the Standard method for calculating the λ1 factor is in cables with non-magnetic armor. Their validity is further enhanced by means of Filament Method. IEC 60287 appears to overestimate the temperature, particularly for larger conductor sizes, by up to 7°C (8%). Finally, suitable Reductive Factors are suggested which could improve the accuracy of the IEC method.
7 November 2017 in IEEE Transactions on Power Delivery
Cables intended to interconnect offshore wind farms with the mainland are currently treated as separate lead-type cables by IEC 60287. A single core equivalent thermal model (SCETM) is implied, that is, a thermal model accounting for 1-D (radial) heat transfer only. While this approach is expected to be reasonable when smaller cables are rated, the 1-D representation is less valid in larger cable sizes. This paper uses 2-D finite-element models to reveal certain weak points of the representation of the thermal resistances in the existing SCETM. For constant losses, the IEC SCETM seems to underestimate the temperature by up to 8 °C. Suitable replacement formulae are proposed that could improve the accuracy of the SCETM. Finally, the issue of nonsolid fillers is considered and modelling guidelines are given.
3 April 2025 in IEEE Transactions on Power Delivery
The rapid growth of offshore renewable energy projects has led to the increased usage of submarine cables, which are necessary for the power transmission to the mainland. In their majority, these are AC, three-core (3 C) armored power cables. The environmental impact of such cable installations has not been fully evaluated yet, although concerns have been raised about potential harmful consequences on the balance of natural ecosystems due to the emitted magnetic field. The armor existence and the twisted cable geometry make the magnetic field calculations in the vicinity of such cables more challenging than existing analytical methods which only consider straight or helically twisted conductors. Other, existing works account for the cable twisting effects when computing the field produced by AC, 3 C armored cables via numerical methods. A more accurate numerical method, accounting for the field-dependent magnetic permeability, is suggested in the present paper. The problem of magnetic field calculation around the cable is approached also analytically and a sufficiently accurate, faster solution is provided. Both methods are validated against experimental measurements, achieving an agreement better than that cited in the literature. Various design aspects, such as the conductor size, armor magnetic permeability and armor lay length, are also discussed.