Expert, intelligent and robust automatic generation control (AGC) scheme is requisite for stable operation and control of power system (PS) integrated with renewable energy sources (RES) under sudden/random small load disturbances. Large frequency deviations appear if AGC capacity is inept to compensate for the imbalances of generation and demand. In this paper, a cascade‐fractional order ID with filter (C‐I λ D μ N) controller is proposed as an expert supplementary controller to promote AGC recital adequately in electric power systems incorporated with RES like solar, wind and fuel cells. The imperialist competitive algorithm is fruitfully exploited for optimizing the controller parameters. First, a 2‐area reheat thermal system is examined critically and then to authorize the worth of the proposed controller, the study is protracted to a 2‐area multi‐source hydro‐thermal system. The prominent benefits of C‐I λ D μ N controller with/without renewable energy sources consist of its great indolence to large load disturbances and superiority over various optimized classical/fuzzy controllers published recently. The sensitivity study validates the robustness of the recommended controller against ±20% deviations in the system parameters and random step load perturbations.
27 December 2020 in International Journal of Energy Research
Regulating the frequency fluctuations (known as load frequency control) in the power system is an important aspect that directly signifies the balance between the generation and demand. The present study proposes an optimal LFC scheme encapsulating the concept of fractional-order based tilted-integral-derivative (TID) controller having optimized parameters using the recently developed optimization technique called salp swarm algorithm. The various non-linearities such as governor dead-band, generation rate constraint, and communication time delays are also considered in the power system having thermal-hydro-wind turbines generating units in both areas. Furthermore, the impact of thyristor controlled phase shifter (TCPS) and redox flow battery (RFB) has been investigated in the proposed power system. Extensive simulations for different test systems and robustness analysis with wide variation in all system parameters at a time have been executed to validate the superiority of the proposed control strategy. The effectiveness of the proposed controller has been studied by comparing system response with recently developed algorithms. The performance evaluations confirm that the proposed controller provides stable, optimal, and superior performance compared to other existing schemes. Further, obtained results strongly suggest that TCPS and RFB units stabilize the transients quickly to enhance the system frequency stability during load instabilities.