4 June 2020 in IEEE Transactions on Industrial Electronics
Verified
Journal Article
Closed access
LZLiming Zheng
Liming Zheng
KJKe Jia
Ke Jia
TBTianshu Bi
Tianshu Bi
YFYu Fang
Yu Fang
ZYZhe Yang
Zhe Yang
In this article, power converters are used in the integrated wind farms and can change the fault characteristics of the power system. The conventional pilot protection suffers from low sensitivity, or even the risk of maloperation. In order to address these problems, the fault features of the transient current of various power sources are analyzed and a novel pilot protection based on cosine similarity is proposed. To validate the proposed protection, the real time digital simulator hardware-in-loop tests are carried out to verify the proposed method. In addition, a field short-circuit test is conducted in a real wind farm to examine the performances of the proposed protection. The results demonstrate that the proposed method can be potential option for industrial applications.

21 August 2020 in IEEE Transactions on Industrial Informatics
Verified
Journal Article
Closed access
KJKe Jia
Ke Jia
ZYZhe Yang
Zhe Yang
LZLiming Zheng
Liming Zheng
ZZZhengxuan Zhu
Zhengxuan Zhu
TBTianshu Bi
Tianshu Bi
The fault current of wind farms (WFs) is significantly different from conventional synchronous generators (SGs) and shows limited amplitude, controlled angle, rich harmonics and strong nonlinearities. Therefore, the traditional differential protection faces the challenge of sensitivity decline and even refusal. In order to solve this problem, a pilot protection based on the Spearman rank correlation coefficient is proposed. When the system operates normally or the external fault occurs, a traversing current is flowing through the transmission line, so the current waveforms on both sides are completely opposite. When an internal fault occurs, there are huge differences in the transient current waveforms on both sides. Therefore, the Spearman rank correlation coefficient can be used to distinguish the faults inside and outside the zone. Compared with existing protection, it shows good performances for all fault situations. Both the simulation results and the field testing data verify the proposed method.

8 October 2021 in IEEE Transactions on Smart Grid
Verified
Journal Article
Closed access
KJKe Jia
Ke Jia
QLQian Liu
Qian Liu
BYBin Yang
Bin Yang
LZLiming Zheng
Liming Zheng
YFYu Fang
Yu Fang
TBTianshu Bi
Tianshu Bi
Fault characteristics analysis normally provides a theoretical foundation for the protection design. Although conventional fault analysis of inverter-interfaced renewable energy sources (IIRESs) can characterize post-fault steady-state at the power frequency, it might not effectively present the fault transient. This can negatively affect the protection based on fault transient data within 20–30 ms after a grid fault. Thus, the fault transient of IIRESs needs to be fully investigated. Given this, the nonlinear effect of controller saturation is considered in this study. The domain of attraction (DOA) is first established to estimate the practical working state of the controller within the current loop. The transient fault current (TFC) analytical model is then proposed in accordance with the nonlinear control response of the controller under different working stages, which reveals a detailed transient transition of the fault current. Meanwhile, the proposed model is low-order and presents high applicability in different fault scenarios. Simulation results indicate that the TFC analytical accuracy obtained using the proposed method is improved by at most 50% relative to the accuracy reported in published studies. Field short-circuit test data are ultimately used to verify the performance of the proposed TFC analytical model.

2 April 2021 in IEEE Transactions on Industrial Electronics
Verified
Journal Article
Closed access
LZLiming Zheng
Liming Zheng
KJKe Jia
Ke Jia
WWWenqiang Wu
Wenqiang Wu
QLQian Liu
Qian Liu
TBTianshu Bi
Tianshu Bi
QYQixun Yang
Qixun Yang
With the integration of the large-scale wind farms, the conventional pilot protection is facing new challenges. It suffers from the performance degradation can even refuse operation for some extreme fault scenarios. To address this problem, this article continues the research of the novel pilot protection based on cosine similarity. The protection pickup setting and industrial application testing is investigated. The functional structure is described and the logic of the cosine similarity based protection is evaluated under different fault scenarios. Compared with the conventional differential protection, application of the proposed protection can greatly improve the relay performance. The proposed protection is embedded into an industry relay device, and the standard hardware-in-loop tests are carried out using the real time digital simulator before the industrial application. Now, the protection device based on cosine similarity is installed in the wind farms and put into operation in Inner Mongolia.

14 February 2020 in IEEE Transactions on Power Delivery
Verified
Journal Article
Closed access
LZLiming Zheng
Liming Zheng
KJKe Jia
Ke Jia
TBTianshu Bi
Tianshu Bi
ZYZhe Yang
Zhe Yang
YFYu Fang
Yu Fang
The wide application of power electronic component in power system with renewable energy sources has changed the fault characteristics of power system, resulting in the performance degradation of conventional protection, and even the risk of malfunction. This brings challenges to the security of the power grid. In order to solve these problems, a novel pilot protection based on structural similarity is proposed. The structural similarity criterion makes use of the difference of fault characteristics between renewable sources and synchronous generators to identify internal faults, while the square error auxiliary criterion is used to solve abnormal calculation of the existing similarity based protection. The detailed model of grid-connected renewable energy power plant is built in Real Time Digital Simulator (RTDS) and the proposed protection algorithm is solidified in the industrial protection device. The effectiveness of the proposed principle is verified by hardware-in-loop dynamic simulation experiments. Compared with conventional differential protection, the proposed protection shows excellent performance in speed and reliability during various faults. In addition, a field short-circuit test is carried out in a real wind farm to verify the effectiveness of the proposed protection scheme. It is proved that this proposed method has the prospect for industrial application.

24 September 2021 in IEEE Transactions on Power Delivery
Verified
Journal Article
Closed access
LZLiming Zheng
Liming Zheng
KJKe Jia
Ke Jia
BYBin Yang
Bin Yang
TBTianshu Bi
Tianshu Bi
QYQixun Yang
Qixun Yang
The modular multilevel converter-based high voltage direct current transmission (MMC-HVDC) technology has become an effective integrating method for large-capacity offshore wind farms. However, if AC side faults occur between the MMC and the wind farm, conventional current differential protection methods based on phasor measurements might not detect the large fault current at the wind farm and the MMC, resulting in poor protection performance. In the worst case, MMC blocking may occur during faults near the MMC station, causing relay refusal. The fault currents provided by both converters are analyzed in detail. Due to the fault-ride-through control objectives, it is proved that the singularity of fault current between wind farms and MMC is different. Therefore, a novel singular value decomposition (SVD) based pilot protection is proposed to solve this problem. A Hankel matrix is established for the short-circuit current at each end of the AC line. The Hankel matrix rapidly detects the singularity of the signal and its derivative, and the SVD method uses a short time window to extract the waveform features. This approach enables the detection of the fault features before MMC blocking in the worst-case fault scenario and prevents the incorrect fault identification caused by the minor amplitude of fault current provided by the converters. A detailed model of an offshore wind farm connected to the MMC-HVDC system is established in the real-time digital simulator (RTDS). A protection device compliant with industry standards is used to implement the SVD-based protection algorithm. Hardware-in-loop dynamic experimental tests are conducted to verify the performance of the proposed protection method. The experimental results demonstrate that the SVD-based protection method has excellent performance during various fault scenarios.