Accurate estimation of fault location is highly crucial for swift maintenance and early power restoration. Since faults in DC networks are time critical, this paper proposes a new fault detection and localization scheme for a low voltage direct current (LVDC) micro-grid network. Low resistance faults are detected by observing voltage across the inductor whereas high resistance ground faults are identified by measuring ground current at the relay location. Thereafter, based on iterative method, fault location is estimated by comparing analytically derived fault current with the measured value of fault current. Genuineness of the suggested technique has been assessed by simulating various internal, external and simultaneous faults on a typical LVDC micro-grid network modeled in PSCAD/EMTDC environment. The proposed method is capable of detecting and locating both low and high resistance DC faults without utilizing remote end quantities. Subsequently, initial guess has minimal impact on the convergence and accuracy of the proposed algorithm. Comparative evaluation of the proposed technique with other techniques clearly proves its superiority in terms of better discrimination against external faults, rapid detection during internal faults, independency on the network topology and higher accuracy for fault distance estimation against all types of internal faults.
1 April 2014 in IET Generation, Transmission & Distribution
Nuisance fuse blowing because of miscoordination between fuse and recloser in power distribution network is very critical issue particularly when distributed generations (DGs) are incorporated. This study presents a new adaptive digital relaying scheme for power distribution network containing DG, which circumvents miscoordination between recloser and fuse. It is based on calculation of the ratio of feeder current and recloser current. With the help of this philosophy, the proposed scheme automatically modifies the time dial setting of the relay and hence enhances margin between fuse and recloser in order to avoid miscoordination between fuse and recloser. The proposed scheme has been extensively tested for various types of faults in radial distribution network containing DG. Fault data are generated by modelling an existing part of 11 kV Indian power distribution network using PSCAD/EMTDC software package. Furthermore, the impact of different DG capacities on the margin (coordination) between fuse and recloser are also analysed. It has been observed that the proposed scheme maintains proper coordination between fuse and recloser for all types of fault. Moreover, it also provides satisfactory operation during high resistance single line‐to‐ground faults.
1 April 2016 in IET Generation, Transmission & Distribution
This study presents random forest‐based fault discrimination technique for power transformer. The proposed scheme relies on extracting features from the measured data of differential current signals of a power transformer. Various simulation cases consisting of internal faults including special types of turn‐to‐turn and primary‐to‐secondary winding faults and other disturbances (over‐excitation and different types magnetising inrush such as initial, residual, recovery and sympathetic) have been generated with varying fault and system parameters for an existing power transformer of an Indian power transmission network using PSCAD/EMTDC software package. The performance of the proposed scheme has been evaluated over a simulation dataset of 5442 cases and the overall fault discrimination accuracy of more than 98% is achieved. The proposed scheme gives promising results for different connections and various ratings of the transformer, even though it is trained only once for a single rating and connection of a transformer. Comparative evaluation of the proposed scheme with the existing scheme clearly indicates the superiority of the proposed scheme as it remains stable during CT saturation condition and gives better stability during disturbances compared with conventional/existing schemes.
28 September 2017 in IEEE Transactions on Smart Grid
An implementation of a new islanding detection technique based on modal components of the voltage signals is presented in this paper. It is based on derivation of Islanding Detection Factor (IDF) which is derived from the modal transformation of the input voltage signals. Authenticity of the presented technique has been verified by developing a laboratory prototype of the distribution network along with Distributed Generator (DG). From the developed laboratory prototype, various islanding cases with varying positive/negative active and reactive power mismatches and different non-islanding events have been generated. The experimental results show that the presented algorithm is able to differentiate between islanding situation and non-islanding events efficiently. Moreover, it is able to sense islanding situation rapidly as it operates within three and half cycles after the inception of event. Furthermore, the proposed scheme is able to identify islanding situation even in case of perfect power balance condition. In addition, the presented scheme provides better stability against various non-islanding events and hence, avoids nuisance tripping. At the end, comparative evaluation of the proposed scheme with the existing schemes clearly indicate its superiority in distinguishing islanding situation with non-islanding events.
This paper provides a comprehensive review of the acoustic method used for partial discharge (PD) localization in power transformer. The paper outlines the partial discharge mechanism, basic principle and properties of the acoustic emission (AE), advantages and limitations of the acoustic method compared to the electrical method, and different AE based PD localization techniques along with their algorithms used in power transformer. Most of the algorithms proposed in the literature for PD localization in power transformer are based on the time difference of arrival (TDOA) of AE signals. Thus, this paper would help researchers, academicians, and engineering communities working in the area of AE based PD localization in power transformer to avoid insulation damage.
22 November 2021 in IEEE Transactions on Smart Grid
Even though the implementation of hybrid AC/DC microgrid is increasing, their protection schemes face multiple challenges such as inconsistent fault current supply from DGs, difficulty in discriminating internal/ external faults and missing of universal protection scheme for both AC and DC distribution networks. In this regard, a unified fault detection and localization scheme is proposed for hybrid AC/DC microgrid. By measuring the impedance at system frequency for AC circuit and at a specific pre-inserted frequency for DC network, the suggested technique achieves proper discrimination between internal faults and external events. Several fault scenarios such as internal/external faults, single/double line faults with varying fault location and fault resistance have been investigated on both AC and DC circuits by modeling hybrid AC/DC microgrid in PSCAD/EMTDC environment. The results reveal the effectiveness of the proposed algorithm in discriminating internal faults with external events and also in estimating accurate fault location even under noisy environment. Finally, a comparative evaluation of the proposed unified AC/DC protection scheme with other individual AC/DC protection schemes shows its superiority in combining both the AC and DC schemes together into a single relay, having an improved fault detection time and an increased fault localization accuracy.