Driven by the pursuit of energy efficiency and carbon neutrality, data-driven models are increasingly adopted for intelligent building energy control, yet their reliability is often compromised by sensor-induced anomalies and missing data. Focusing on active phase change wall (APCW) systems, this study systematically compares four reconstruction methods: moving average (MA), adaptive singular value decomposition (ASVD), Kalman filtering (KF), and Gaussian process regression (GPR), to mitigate measurement distortion. The investigation utilizes data distortion issues observed in experiments conducted on a scaled-down test platform to evaluate the performance of nine prediction models under extrapolation to unknown operating conditions and robustness testing, incorporating the four data reconstruction strategies. This evaluation was achieved through the integration of these models and the application of time-series-aware hv-blocked 5-fold cross-validation. Finally, controlled fault injection was employed to simulate three typical fault types: drift, sudden change, and noise, systematically assessing the effectiveness and applicability of each data reconstruction method in rectifying faulty data. Results show that ASVD, KF, and GPR improve extrapolation performance for most models; KF delivers the largest error reductions, achieving RMSE and MAE decreases of 71.4% and 73.8% for PTL relative to MA. Under strategy-switching robustness tests, GPR yields consistently positive gains across all models, and the best overall pairing (GPR–LSTM) reduces RMSE by up to 70% compared with ARIMAX. Controlled fault injection tests indicated that GPR was most effective against drift and noise faults. Under drift conditions, the RMSE with repaired data was approximately 56 times lower than that of the MA method, while MA was most effective in the event of sudden faults.Overall, the proposed framework provides empirical guidance for improving fault-tolerant APCW modeling in real-world deployment.