We propose a chance-constrained formulation for the problem of dimensioning frequency restoration reserves on a power transmission network. We cast our problem as a two-stage stochastic mixed integer linear program, and propose a heuristic algorithm for solving the problem. Our model accounts for the simultaneous sizing of both upward and downward reserves, and uncertainty driven by imbalances, contingencies and available transmission capacity. Our core methodology is further adapted in order to minimize inter-zonal flows and in order to split reserve requirements between automatic and manual frequency restoration reserves. We apply our methodology to the problem of sizing reserves in the four load frequency control areas of the Swedish power system. We demonstrate the benefits of our method in terms of decreasing reserve requirements in the absence of reserve sharing, we analyze the spatial allocation of reserves, and we perform various sensitivity analyses.
In order to cope with intra-zonal grid constraints, we propose a hierarchical paradigm for organizing balancing and congestion management in European zonal markets. Our approach relies on an aggregation function which converts balancing market offers to zonal market offers that adhere to the bidding format of European balancing platforms, followed by a disaggregation function for dispatching and settlement which represents physical constraints of network flow. We investigate various design choices related to our proposed aggregation-disaggregation paradigm. We test our proposed methodology on a 46-node model of the Nordic system by reporting on a variety of technical and economic performance metrics.