During the process in which a vacuum circuit breaker (VCB) switches off the shunt reactor (SR), an overvoltage with high amplitude and high frequency (HF) will occur because of current chopping and multireignition. To reproduce this switching overvoltage faithfully, the voltage and current characteristics of the VCB were analyzed in this work, based on the field test data from a 220-kV substation in Chongqing, China. Then typical parameters of three basic factors mentioned in Helmer's VCB model, chopping current value, dielectric dynamic insulation strength and HF current quenching capability, were selected after statistical analysis and an arc reignition model of VCB was established. Based on this presented model, the influences of the surge arrester, the resistor-capacitor (RC) snubber and the installation positions and quantities of these protective devices on overvoltage suppression performance were studied in simulation. In addition, the field test using surge arrester and RC snubber as the suppression measures was performed again in the same substation. Finally, we derived the conclusion that the most suitable suppression scheme for overvoltage caused by VCB switching off 10-kV SR is installing two 12/32.4 kV surge arresters at the terminals of the cables for the SR and the substation transformer (ST).
17 November 2021 in IEEE Transactions on Power Delivery
A 10 kV vacuum circuit breaker (VCB) experiences prestrikes when its contacts are closing. Prestrikes can cause a high frequency (HF) and steepness overvoltage, which compromise the insulation of electrical devices. The transient prestrike process should be accurately simulated to effectively design and evaluate overvoltage suppression measures. The improved prestrike model was modeled in ATP-EMTP based on on-site measurement prestrike data. The model was applied to compare various overvoltage suppression measures in terms of the effectiveness. The simulation results showed that an RC snubber and a surge arrester can be installed to suppress the overvoltage amplitude on the substation transformer (ST) and shunt reactor (SR) sides. The RC snubber can reduce the oscillation frequency of the overvoltage compared with the surge arrester. Finally, the RC snubber and surge arrester were installed on the ST and SR sides as part of a field test to verify the simulation results. Reasonable suggestions are provided for switching overvoltage suppression through the simulation and experimental results.