Three installation-level lithium-ion battery (LIB) energy storage system (ESS) tests were conducted to the specifications of the UL 9540A standard test method [1]. Each test included a mocked-up initiating ESS unit rack and two target ESS unit racks installed within a standard size 6.06 m (20 ft) International Organization for Standardization (ISO) container. All tests were conducted with an identical LIB configuration. The initiating unit rack included nine modules (2,430 individual 18650 form factor cells) with a total capacity of 28.9 kWh. The target unit racks were loaded to one-third capacity of the initiating unit with nine partial modules and a total capacity of 9.6 kWh. All cells in the container were charged to 100% state-of-charge and none were electrically connected. Within the initiating mock-up unit, a flexible film heater was wrapped around an individual 18650 form factor cell. This instrumented 18650 cell was heated at a rate of 6°C/min to initiate thermal runaway.
This report covers results of experiments conducted to obtain data on the fire and deflagration hazards from thermal runaway and its propagation through energy storage systems (ESS). The UL 9540A test standard provides a systematic evaluation of thermal runaway and propagation in energy storage system at cell, module, unit, and installation levels. The data from this testing may be used to design fire and explosion protection systems needed for safe siting and installation of ESS. In addition to temperature, pressure, and gas measurement instruments installed inside of the container, fire service portable gas monitors were placed at locations inside and outside the storage container during the experiments to assess their ability to detect products of thermal runaway and inform fire service size-up decisions. Review section 2.2.3 Fire Service Size-up Equipment to learn more. This research demonstrates a clear need for responding firefighters to have early access to data from instrumentation installed within an ESS, particularly gas measurement instrumentation, available through a monitoring panel. Additionally, it highlights the importance of communication between responding firefighters and personnel responsible for management of the ESS, who can aid in complete evaluation of system data to develop a more clear picture of system status and potential hazards.