19 September 2018 in IEEE Transactions on Power Electronics
This letter presents an adaptive frequency locked loop with fixed-length transfer delay units for single-phase systems. By analyzing the relationship between the grid voltage and its transfer delay signals, a linear regression model of the grid voltage is established. Accordingly, a transfer delay-based adaptive frequency locked loop (TD-AFLL) is proposed. A mathematic proof indicates that the proposed TD-AFLL can reject both phase offset errors and double-frequency oscillatory errors. Thus, the grid voltage parameters can be estimated accurately, even when the frequency drifts away from its nominal value. Moreover, fast dynamics of the TD-AFLL are achieved due to the transfer delay structure. Experiments verify the effectiveness of the proposed method.
11 June 2019 in IEEE Transactions on Industrial Electronics
In aircraft grids, the voltage frequency is much higher than that in utility power systems and it challenges the dynamics of frequency estimations. In this letter, a fast and robust frequency estimation method is proposed for aircraft grids even when the grid voltage is distorted. In detail, a mathematical model is established based on the relationship among the fundamental grid voltage, harmonics and their time-delay signals. Accordingly, a robust parameter identification method is proposed to achieve grid frequency estimation and harmonic immunity. Compared with the frequency estimations for utility power systems, the proposed method, so-called robust frequency estimation (RFE), has faster dynamics and stronger harmonic suppression capability. Hence, it takes advantages in the applications of aircraft grids. Experimental results also indicate that the proposed RFE has good performance in terms of fast dynamics and strong robustness.
2 October 2019 in IEEE Transactions on Industrial Electronics
Phase-locked loops (PLLs) are widely popular in applications of grid synchronization for single- and three-phase utility power systems. However, these PLL-based methods are usually designed for constant frequency grids and these schemes only have fast dynamics and good accuracy in a small local region (i.e., phase locked region). When applying these PLLs in the grids of more electric aircraft (MEA), in which the grid frequency varies in a wide range (360 Hz-800 Hz), both the dynamic response and the steady-state accuracy of PLLs reduce significantly. In light of this, this paper presents a global convergence method to estimate the frequency, positive- and negative-sequence components of grid voltage in MEA power systems. By analyzing the relationship between the DC-offset component, the grid voltage and their derivatives, a mathematic model with the unknown parameters, which are the DC-offset component and the grid frequency, is established. Accordingly, a global estimator is proposed to estimate the grid voltage parameters accurately. A Lyaponov-based argument ensures that the proposed estimator is global convergent and it has the capability to eliminate the DC offset effect completely. The experimental results are provided to verify the effectiveness of the proposed estimator.
31 December 2019 in IEEE Access
Estimating the amplitude of the grid voltage is important for low-voltage ride-through (LVRT) operation in single-phase systems. It requires fast dynamics and is typically achieved through a phase-locked loop (PLL). This paper proposes a fast amplitude estimation (FAE) method without a PLL structure. The grid voltage is formulated as a vector sum of sine and cosine functions, resulting in an algebraic model with two unknown parameters. The proposed FAE identifies the two parameters, and thus achieving a fast fault detection (i.e., the amplitude estimation). Experimental results verify the performance of the proposed method in terms of fast dynamics.