1 January 1999 in IEEE Transactions on Dielectrics and Electrical Insulation
22 June 2020 in IEEE Transactions on Power Delivery
In High Voltage Direct Current (HVDC) systems, composite outdoor insulators play a critical role and focus is needed on the research of their failure. In the case of a pole to ground fault of a bipolar scheme, the healthy pole experiences an overvoltage similar to a Switching Impulse (SI) superimposed on the operational DC voltage. However, there is no standard test for such voltage superimposition. This paper investigates the performance of a composite insulator stressed with such superimposition under dry and rain conditions. To determine the direct voltage influence on the flashover voltage, the results have been compared with the SI only case. Four different rain conductivities have been used in the test programme. Both vertical and horizontal orientations have been studied. Most cases show that direct voltage pre-energisation has a negative impact on the flashover performance. The increase in rain conductivity leads to lower flashover values, and the horizontal orientation outperforms the vertical configuration. Under these test conditions, the flashover voltages were all larger than a typical DC operational switching surge. Thus, in the case of pole to ground fault, the healthy pole failure risk seems small. Further research is needed on higher voltages and polluted conditions.
1 January 2001 in IEE Proceedings - Generation, Transmission and Distribution
Zinc-oxide (ZnO) surge arresters are now well established as a very efficient and reliable form of overvoltage protection against both fast surges, such as those generated by lightning and gas-insulated switchgear, and high-energy surges generated by switching operations and temporary faults on the network. The addition of ZnO surge arresters to existing protection schemes reinforces the system's reliability and the security of supply. The protection characteristics of the parallel configuration formed by arresters and existing spark gaps at distribution voltages are studied. Tests on various spark-gap geometries, with and without surge arresters in parallel, have been carried out to determine breakdown characteristics, probability curves and voltage–time characteristics for different impulse shapes. It is found that the introduction of the arrester in the circuit modifies the prospective impulse which results in the shift of the breakdown characteristics towards higher voltages. A proposed circuit model, based on laboratory test data, is used to simulate such parallel configurations. Good agreement between test and simulated results is obtained. As a result of these tests, it is recommended that gap-sparkover characteristics based on short-tail (about 5µs) impulses are used for insulation co-ordination. The role of parallel airgaps in preserving the arrester energy-rating limits is also discussed.
4 September 1996 in IEE Proceedings - Science, Measurement and Technology
An alternating-current corona model is adapted to allow its application to fast transient overvoltages in coaxial geometries. An initial study of data for positive and negative lightning and switching impulses shows good agreement between the model and experiment. Application is then made to a negative corona under oscillatory impulses with frequencies of 33 and 125 kHz. The model is used to aid interpretation of the complex experimental results, and gain an insight into the underlying physical phenomena. A semi-quantitative adaptation is then made to successfully simulate experimental data. The model is shown to be applicable to all voltage types including direct, alternating and impulse voltages.