The article presents a methodology for three-position discrete control of ventilation systems in the premises of energy enterprises with an increased risk of forming explosive gas environments. The focus is on two typical sources of hazardous gas accumulation: methane, released in rooms with gas-fueled power generator units, and hydrogen, generated while charging lead-acid batteries in accumulator rooms. The proposed approach enables the transition from two-position (“On-Off”) control to a three-position ventilation drive control mode using an adaptive characteristic derived from a PID controller with predefined parameters. The control is implemented through an asynchronous electric motor with a “star–delta–off” switching scheme, allowing the exhaust ventilation operation mode to adjust automatically. The automation of the system is based on an IoT device that supports integration into a local information-control network, measures temperature and flame presence, and transmits data via the industrial ModBus TCP protocol. System operation modelling was performed in MATLAB Simulink, including implementing the adaptive characteristic subsystem, its conversion into a three-position control signal, and a dynamic model of ventilation behaviour under varying gas concentrations. The results confirm the stable operation of the ventilation system, effective reduction in methane and hydrogen concentrations, and decreased energy consumption through optimized fan control. The proposed methodology allows classical control algorithms to be adapted for discrete actuator operation and enables seamless integration of ventilation subsystems into modern automated energy infrastructure.