13 March 2017 in IEEE Transactions on Smart Grid
Microgrid is an effective means to integrate distributed generation (DG) resource. However, uncertain renewable DG such as wind turbine and photovoltaic outputs and load demands can introduce tremendous difficulties for energy management in microgrids. To mitigate such difficulties, price-based demand response (PBDR) can adjust the loads to adapt to the renewables. On the other hand, dispatchable DG such as microturbines can coordinate with the PBDR to further manage the power balance and achieve economic benefits. In this paper, a two-stage robust microgrid coordination strategy is proposed: a PBDR is scheduled a day ahead and microturbine outputs are modified hourly. A two-stage robust optimization model is proposed to address the coordination problem with guaranteed robustness against the uncertainties of renewable DG and load demands. Simulation results show PBDR and multiple DG units can coordinate effectively to accommodate the renewable and demand uncertainties while maximizing the microgrid benefits.
27 August 2018 in IEEE Transactions on Power Systems
High penetration of wind energy in the modern power system exposes the need of smoothing the fluctuating output power in an effective and conducive way. In this context, this paper proposes two novel control strategies that utilize the self-capability of permanent magnet synchronous generator based wind turbine to realize power smoothing. The first strategy pursues to offer power smoothing support via simultaneous utilization of DC-link voltage control, rotor speed control and pitch angle control. The second control strategy seeks to coordinate the three concerned individual control schemes in a hierarchical manner, where the power smoothing tasks are allocated to individual control modules or their combinations dynamically in line with WT's operation status. Both two strategies are able to provide power smoothing support by fully exploiting wind turbine's self-capability, whereas the second strategy has the merits on 1) reducing the activation frequency of pitch angle control, and 2) enhancing wind energy harvesting. Case studies of the proposed control strategies are carried out to compare and verify their effectiveness in achieving power smoothing.
27 July 2017 in IEEE Transactions on Power Systems
Conventional VAR compensation devices such as capacitor banks and synchronous condensers, after long periods of service, have become aged and less effective to satisfy stringent requirement of short-term voltage stability in high-level wind power penetrated power systems. STATCOMs with a rapid and dynamic reactive power support capability can be an ideal alternative, when combined with a proper equipment retirement and upgrades scheme. This paper proposes a systematic approach for optimal dynamic VAR resource planning and upgrading for a power system with increased wind power penetration and equipment retirement. The problem is constituted by two parts that are aged equipment retirement and new equipment placement. A multiobjective optimization model is proposed to minimize three objectives: the cost of retirement and upgrades, the index of proximity to steady-state voltage collapse, and the index of transient voltage unaccepted performance. To simulate real-world operating situation, multiple contingencies and uncertain dynamic load models are taken into account. Furthermore, low- and high-voltage ride through abilities for wind farms are modeled. The proposed model is tested on the New England 39-bus test system.
8 March 2017 in IEEE Transactions on Power Systems
In this paper, a hierarchical security-constrained optimal power flow (SCOPF) model is proposed for a meshed ac/multiterminal HVDC (MTDC) system with high wind penetration. The two interacting levels in the proposed model are as follows: 1) the high level is a traditional SCOPF problem in an ac system that aims to minimize total generation and security control costs; and 2) the low level is a dynamic power dispatching problem, which regulates power flow in an MTDC grid according to reference signals from the high level. Thus, the proposed method utilizes an MTDC system to provide support for the ac system by redistributing power flow across the entire grid and reducing control costs. Two modified IEEE meshed ac/dc systems are used to demonstrate the performance of the proposed method.
2 August 2016 in IEEE Transactions on Smart Grid
The increasingly widespread utilization enables plug-in electric vehicles (PEVs) to provide ancillary service and support economic and secure operation of power systems. This paper proposes a novel model to optimize day-ahead spinning reserve requirement (SRR) considering PEVs' contribution in providing operating reserve. Based on the probabilistic criteria, the cost of expected energy supplied by PEV (EESEV) is formulated. The costs of reserves from thermal generators and PEVs as well as expected energy not supplied (EENS) are considered together to determine optimal SRR. The post-contingency PEV reaction time is taken into account in the formation of EENS and EESEV. The capacities of PEV interruptible charging demand and vehicle to grid service are calculated, respectively, under the conditions of both immediate charging and smart charging strategies. The effects of PEVs on system SRR quantification, unit commitment are comprehensively analyzed using IEEE reliability test system. Numerical results systematically demonstrate the effectiveness of PEVs' participation on the reduction of operation costs and the improvement of power system reliability. Sensitivity analysis of PEV penetration level and compensation cost to PEV owners is compressively conducted to provide meaningful reference for future implementation.
24 October 2017 in IEEE Transactions on Energy Conversion
Under Maximum Power Point Tracking (MPPT) control, wind power is not dispatchable and can be highly disturbing to the supply-demand balance control in particularly context of microgrid. To effective dispatch wind power according to e.g. operator command or market schedule, a variable utilization level (UL) scheme is proposed for a wind power plant (WPP) to fulfill the dispatch order while reducing the loss of total energy production. Considering different wind conditions, the proposed scheme directs the power output for each wind turbine (WT) according to a specific utilization level (UL), which is adaptively adjusted according to WT rotor speed so that less reduction of energy production can be ensured. Meanwhile, more rotational kinetic energy (KE) stored can be stored in WPP, which can be later released for system support when needed. The proposed variable UL scheme is fully investigated in a doubly fed induction generator (DFIG)-based WPP and the results clearly indicate the proposed scheme can harvest more energy than the conventional same UL one while fulfilling the dispatch demand.