Protection performance is characterized by qualities that include selectivity, speed, sensitivity and stability. Generally, selectivity and speed present conflicting requirements on the protection design, as do sensitivity and stability requirements. The integration of distributed generation (DG), in particular at the distribution level, further compromises satisfactory achievement of these performance qualities. A recent paper by the authors introduced a protection algorithm based on active power differential and sensitivity analysis (APdSA) for the protection of active distribution systems and microgrids. This paper investigates the performance characteristics of this algorithm with respect to selectivity, sensitivity, stability, and speed. It is shown that, with an important modification to the protection zoning arrangement, the APdSA algorithm is able to selectively clear faults in a DG-integrated distribution system with high sensitivity, stability, and speed, with more than 95% reach over a wide range of fault resistances. The algorithm is also tolerant to communication failure.
2 September 2023 in Engineering Science and Technology, an International Journal
The integration of distributed energy resources (DERs) has been shown to impact the operation of time-current graded protection schemes traditionally used on the distribution system leading to possible loss of selectivity. This paper presents the development of a voltage-actuated microprocessor-based relay prototype based on a new type of protection algorithm, the Distributed Differential Fault Detection and Identification Algorithm (DDFDIA), introduced by the authors in a recent paper. A Programmable Automation Controller (PAC) is used as the hardware development platform for the prototype. The performance of the prototype is evaluated through tests using an automatic relay test set and voltages derived from simulation results performed in Digsilent PowerFactory and stored in COMTRADE-format files. The results show that the new relay type is capable of providing high speed protection using voltage magnitude and phase angle information only.