19 June 2023 in IEEE Transactions on Industrial Electronics
A second-order model is developed to describe the essential behavior of the grid-following converter (GFLC) and the grid-forming converter (GFMC) for studying the synchronization characteristics of grid-connected converter systems. In this article, a general set of criteria in terms of the manifolds and saddle quantity is derived for studying the homoclinic bifurcation behavior of GFLCs and GFMCs. It is shown that three unstable periodic orbits and two homoclinic bifurcations may exist for the GFLC, while only one stable periodic orbit and one homoclinic bifurcation may exist for the GFMC. It is also found that after the onset of the first homoclinic bifurcation, the stable equilibrium point (SEP) is surrounded by the stable manifolds of the unstable equilibrium point (UEP), which forms the SEP's basin of attraction, for both GFLCs and GFMCs. In this case, the converters may lose their synchronization if the trajectory crosses over the UEP. Therefore, system parameters should be designed to avoid the onset of the aforementioned bifurcation so that the SEP's basin of attraction can be significantly enlarged to contain the UEP. As a result, the GFLC or GFMC can eventually resynchronize with the grid even when its trajectory passes the UEP. Finally, experimental results are provided to verify these theoretical findings.
9 August 2023 in IEEE Transactions on Power Electronics
The widely deployed grid-following converters (GFLCs) may lose synchronization under grid disturbances, presenting a critical challenge to the power electronics penetrated power grid. Existing methods for analyzing transient synchronization stability often assume an ideal current loop in order to keep the system model at low order. However, such approaches based on a simplified second-order model can lead to optimistic stability prediction and inappropriate design. This paper applies a full-order model to explore the effects of the nonideal current loop. The unstable periodic orbits (UPOs) that determine the basin of attraction of the stable equilibrium point are located via a numerical continuation method. Moreover, the essential bifurcations leading to the emergence and disappearance of UPOs are identified. A design principle with consideration of the effects of the nonideal current loop is derived to enhance the transient synchronization stability of GFLCs. Experimental results are provided to verify the analytical findings.
16 October 2024 in IEEE Transactions on Power Electronics
Transient stability analysis of grid-connected converters can provide guidance for practical design. Previous studies have summarized monotonic relationships between stability and parameters. Given the complex nonlinear behavior of converter-based systems, these monotonic relationships are incomplete. In this article, design guidelines in the form of feasible parameter ranges are developed. Sensitivity analysis and bifurcation diagrams are utilized to derive feasible parameter ranges from typical stability analysis methods, including time-domain simulation, energy-based methods (manually derived and algorithmically searched), and bifurcation analysis. It is found that different analysis methods may provide equivalent design guidelines due to the similar sensitivity patterns identified by these methods. Furthermore, we reveal that the change in the sensitivity patterns can be induced by the bifurcation behavior of grid-connected converters. Therefore, the qualitative differences between the stability analysis methods are determined by their ability to capture the various bifurcations crucial for determining transient stability. Our results show different levels of consistency between the analysis methods. The findings are verified by laboratory experiments.
27 September 2022 in Applied Energy
17 May 2024 in IEEE Transactions on Power Electronics
In this article, the impact of pinning-based and consensus-based distributed secondary control on the stability of islanded microgrids is studied. A nonlinear model of the islanded microgrid is first established, incorporating the voltage-loop dynamics and communication delay. Using this model, the influence of the secondary control on the microgrid's dynamical behavior is explored, and in particular, the improved robustness and stability contributed by the voltage-increment-based secondary control is highlighted. Besides, the effects of the topology of communication networks and the selection of driver controllers on the system stability are revealed, and such effects are quantitatively measured by the algebraic connectivity and the conditional number. Moreover, small-signal models and the corresponding loop gains are derived for expediting the selection of suitable secondary control parameters. Furthermore, a design procedure of the distributed secondary control system is demonstrated. Finally, analytical findings are verified by cycle-by-cycle full-circuit simulations and laboratory experiments.
12 June 2024 in IEEE Transactions on Sustainable Energy
Ensuring reliable operation of renewable energy sources requires robust grid-connected converters. Depending on the choice of synchronization methods, grid-connected converters may exhibit distinct nonlinear behavior that plays a vital role in determining their transient stability. Recently, the grid-voltage-modulated direct power control (DPC) has been proposed as an alternative to the conventional phase-locked loop (PLL) to enhance the dynamic response of the grid-following converter (GFLC). However, existing studies have primarily treated the DPC-based GFLC as a linear system. In this paper, we investigate the nonlinear behavior of this converter under weak grids using a large-signal model based on double reference frames. Our findings reveal that the DPC-based GFLC demonstrates sustained oscillation. Interestingly, the stable periodic orbit observed does not arise from a Hopf bifurcation but rather a saddle-node bifurcation of periodic orbits. This critical bifurcation is characterized by the coexistence of a stable periodic orbit and a stable equilibrium point, resulting in a sudden contraction of the converter's stability region. Furthermore, we provide a comparison between the nonlinear behavior of PLL-based GFLCs and DPC-based GFLCs. To validate our findings, we present full-circuit simulations and laboratory experiments.