This article analyzes the performance of different filtering techniques applied to the phenomenon known as partial discharges (PD), which occur in electrical insulation and, when undetected, can evolve into serious failures, such as short circuits and power outages. Therefore, PD analysis becomes an essential tool in the operation, maintenance, and asset management of power grids, since identifying these PD pulses is not trivial due to the presence of noise from both internal and external sources within the power systems, such as adjacent equipment and pollution levels. The study compared filtering and analysis methods on non-invasive measurements made with a high-frequency current transformer, evaluating traditional digital filters, adaptive techniques, and the wavelet transform (WT). A set of seven metrics was used to verify their effectiveness in minimizing noise and preserving signal characteristics, such as signal-to-noise ratio (SNR), cross-correlation (CC), and root mean square error (RMSE), among others. The results demonstrated that advanced approaches, such as the use of adaptive filters and wavelet combinations, outperform classical methods, reducing noise in measurement signals and favoring clearer detection of PD pulses in real data. This contribution improves monitoring and increases reliability in high-voltage electrical systems.