19 May 2026 in IEEE Transactions on Power Electronics
A key objective of the UK's first medium-voltage dc (MVdc) project, Angle-DC, is to reduce network losses, with converter losses (around 10%) presenting significant improvement potential. To reduce the converter's switching losses, this paper presents a power-routing based coordination control strategy for the interleaved input-series-output-parallel (ISOP) converter used in Angle-DC. The control method optimizes power redistribution across submodules (SMs), with high-power SMs operating at low switching frequencies to handle most power transmission, while a low-power auxiliary SM employs fast-response hysteresis control to mitigate the total current ripple, thus reducing losses without compromising output current performance. A hardware-in-the-loop (HIL) test validates the proposed approach, showing a 38% reduction in switching losses compared to conventional power balancing methods for a full-rating system. The effectiveness of the proposed control is further partially validated using a laboratory-scale testbed.