A capable and cost-effective protection scheme is essential for the reliable operation of a microgrid. Conventional impedance measurement-based protection is hindered by shorter line lengths, lower line reactance-to-resistance ratios, and fault ride-through (FRT) of inverter-interfaced distributed generators (IIDGs) in microgrids. They are prone to malfunction due to the remote end infeed current during non-metallic faults. This paper addresses this challenge through the coordination of control and protection. IIDGs are configured to actively inject a small harmonic voltage component into the microgrid after fault while coping with FRT requirements using a dual-frequency controller. A hybrid injection activation criterion is embedded to ensure coordinated harmonic injection and equal participation from all IIDGs. Consequently, a uniform harmonic-frequency voltage potential can be generated throughout the microgrid, and its impact on IIDGs' FRT is minimized. The feasibility of the proposed scheme is verified on a hardware-in-the-loop (HIL) experimental platform, and its enhancement to protection performance is validated through theoretical and simulation studies. It is revealed that the proposed control scheme can significantly reduce the fault location error and facilitate the application of single-ended impedance measurement-based protection in microgrids.