In order to improve the performance of the conventional guided wave testing (GWT) with a low sensitivity on damage in pipelines, a new GWT based on time-frequency-domain reflectometry (TFDR) is proposed. TFDR using electromagnetic signals is a diagnostic technique for electrical cables, and the signal is analyzed in both time and frequency domains to enhance the resolution of faults in the electrical cables. Since it is impossible to directly apply the TFDR methodology for electrical cables to the pipelines, this article presents new TFDR methodologies suitable for the ultrasonic characteristics of the pipelines. The proposed technique is demonstrated by experiments using a real-world pipeline. The analysis of the experimental results depending on the changes in the defect size and internal material of the pipeline is provided, and the performance of the proposed technique is confirmed by the experiments.
16 January 2017 in IEEE Transactions on Applied Superconductivity
A high-temperature superconducting (HTS) cable system with the 22.9 kV, 50 MVA, and 410 m length is installed and operated at 154 kV Icheon substation of Korea Electric Power Corporation (KEPCO). Unfortunately, it is a difficult task to diagnose and monitor electrical and thermal characteristics of the HTS cable system in a real-time manner. In order to protect operational failures of grid-connected HTS cable systems, this paper proposes time-frequency domain reflectometry (TFDR) and analysis techniques, i.e., time-frequency cross correlation and instantaneous frequency estimation. To verify the performance of the proposed method, the temperature is changed via the cryogenic refrigeration system and the status of the grid-connected HTS cable is monitored via TFDR in a real-time manner.
22 November 2018 in IEEE Transactions on Industrial Electronics
In this paper, new time-frequency-based anomaly detection methodology is proposed for the condition monitoring of high-temperature superconducting (HTS) cable systems. The time-frequency-based anomaly detection methodology includes two indices, which are obtained via cross Wigner-Ville distribution and scattering parameter. For the validation of the proposed methodology, the methodology is applied to an ac 22.9-kV/50-MVA HTS cable system connected to the real power grid network. Furthermore, the changes in dielectric properties of the HTS cable system during the cooling process and the current imbalance failure are monitored. The proposed anomaly detection indices are shown to be able to detect the heat and the current imbalance caused by the malfunction of the joint box. For the application of the two validated indices, new anomaly detection procedure for HTS cable systems is also presented.
27 February 2018 in IEEE Transactions on Applied Superconductivity
In this paper, we propose a new time-frequency based analysis method that monitors the state of the high temperature superconducting (HTS) cable system in a real-time manner and detects the current imbalance of HTS cable system. The new time-frequency-based method utilizes the cross Wigner–Ville distribution to analyze the time-frequency localized phase difference of the reflected signal, which varies depending on the insulation characteristics of the HTS cable system. Also, a real-world AC 22.9 kV 50 MVA HTS cable system and a current source are used to validate the performance of the new monitoring method in order to detect current imbalance phenomenon.
6 October 2021 in IEEE Transactions on Industrial Electronics
Low-voltage shielded cables serve critical roles in controlling and measuring advanced power systems to ensure their reliability and safety. As a consequence, it is important to monitor the cables. However, conventional monitoring techniques for nonoperating power systems are limited regarding safety issues that eventually affect the reliability of a power system and result in economic losses. In this article, a contactless signal communication approach via an inductive coupler is applied to stepped-frequency waveform reflectometry to monitor operating power systems. Additionally, a long short-term memory (LSTM)-based neural network model is adapted to compensate for the nonlinear distortion in signals yielded by couplers. Compared to conventional approaches, LSTM has advantages, as it can restore the nonlinearities of couplers because it can respond to various nonlinear factors, such as the dimension of the coupler, the length of the cable, or the position of the signal application. The proposed reflectometry system for monitoring live shielded cables is tested on 75-m 2-core shielded cables with two cases of fault simulations, and the efficacy of the proposed technique in real fields is also verified.
7 March 2019 in IEEE Transactions on Applied Superconductivity
The characteristics of the HTS cable including conductivity, permittivity, and insulation characteristics vary depending on the conditions of temperature and pressure during operations. We propose a diagnostic method that estimates the propagation constant of the HTS cable and detect the location and the degree of the fault using stepped frequency waveform reflectometry. The performance of proposed method is verified by the HTS cable experiment regarding the propagation constant estimation and the fault detection. The results of HTS cable cooled by the liquid nitrogen are also compared with the results at the room temperature to analyze the insulation characteristics change according to the state. The proposed method is expected to be further applied to monitor the condition of HTS cable system regarding temperature and pressure.