To mitigate the impact of extended power outages from extreme weather events, utilities are trying to improve the existing restoration practices by adopting many emerging technologies. The coordination will be more complicated when emerging participants such as EVs are expected to provide grid services during restoration and customers are demanding less impact. In this paper, an integrated coordination formulation for service restoration, crew dispatch, and EV dispatch with distributed energy resources (DER) control is proposed. A unified routing-based model is used to model separate problems with the same set of equations to provide easy coordination. A novel routing-based EV dispatch formulation with two new tables - state of charge (SOC) status table and SOC exchange table - is proposed to track EV energy change during the routing process. The functional interdependencies among the sub-problems are investigated and leveraged and different DER control modes are developed and integrated. Case studies are conducted on the modified IEEE 123 node test system to showcase the effectiveness of the proposed model for capturing the interdependencies and demonstrate the concept of using EV and other emerging technologies for service restoration.
A digital twin virtually and dynamically represents a physical asset, system, or process in the digital world. This digital counterpart mirrors the real-world entity in its behavior, characteristics, and interactions by utilizing real-time data and simulations. Essentially, it serves as a bridge between the physical and digital worlds, offering a comprehensive view of the asset’s performance and functionality.
This paper reports results from analysis of low-frequency oscillation monitoring on the Western Interconnection of the North American power system from a distribution-level phasor monitoring network (FNET). Some examples of oscillation characteristics excited by various disturbances are discussed using real measurements taken in 2010. The Matrix Pencil method is used for oscillation modal analysis. Analysis results provide a dynamic profile of inter-area mode distribution in the Western Interconnection. Results from this study generally agree with earlier observations.
A fast islanding detection tool can help power dispatchers monitor and control power system operations. Frequency monitoring network (FNET) is a low cost and quickly deployable wide-area phasor measurement system at the distribution level. The frequency disturbance recorder (FDR) in FNET is actually a single-phase phasor measurement unit (PMU) in the sense that it measures the voltage phase angle, amplitude, and frequency from a single-phase voltage source. Based on the data collected by the FDRs deployed in the North American power grid, two islanding detection methods, the frequency difference method and the change of angle difference method, are proposed. The six cases, including islanding cases, a generation trip case and a load shedding case, are presented to verify the proposed methods of islanding detection. The results show that the proposed methods can correctly detect power system islanding, and will not be falsely triggered by generation trips and load shedding.
This work targets on the chiller plant operation management for a large campus building cooling load. In this paper a multi-layer optimal chiller operation management framework is proposed to operate various chiller units to meet the system cooling load while reduce the system operation cost. The first layer is the day-ahead 24-hour chiller operation planning layer which optimizes multiple chiller sequencing and chillers loading. The second real-time dispatching layer effectively addresses load forecasting uncertainties in real-time. The load uncertainty is solved hierarchically through two steps of approaches. An efficient and accurate system modeling framework for optimization is formulated with mixed-integer linear expressions to reduce the computational complexity. The effectiveness of this proposed management framework is demonstrated for an actual chiller plant operation in university campus. Simulation analyses validate that the proposed method can effectively address various levels of forecast uncertainty and reduce the operation cost.