Fast emerging fault current levels in high voltage direct current (HVDC) systems has always been a significant obstacle to building a safer and more reliable grid. Inductive fault current limiters (FCLs), compared with its resistive counterpart, are very effective in restricting the fault rising speed that causes major damage during the whole fault process. In this study, a comprehensive review of the methods used for building inductive type FCLs in HVDC systems is presented. The fault current characteristics of the modern HVDC system is discussed to obtain the basic requirements for the FCL. On the basis of different technological domains, various inductive-type FCL topologies and devices are well categorized and analyzed. After the overall discussion and comparison, representative works, as well as new progress and future prospects, are conveyed in detail. One may find the content of this study helpful as a detailed literature review or a practical technical guidance of this field.
11 October 2019 in IEEE Transactions on Power Delivery
The inductance of a permanent magnet-biased saturated fault current limiter (PMFCL) increases automatically with the fault current. It can quickly restrain the rising speed of direct current (DC) fault current. However, when the DC circuit breaker (DCCB) opens, the PMFCL will delay the current drop speed and generate overvoltage, which will increase the voltage stress on the DCCB. In this paper, a new type of fast-response FCL (NFCL) is proposed. It has the advantage of improving the fault current drop speed. Besides, it can reduce DCCB overvoltage, thus protecting the expensive insulated gate bipolar transistors (IGBT) in the DCCB. In addition, it greatly reduces the energy absorption in the DCCB, thus reducing its manufacturing cost. The NFCL operates automatically without a control device, which means that it responds faster. Moreover, the diode is on the low-voltage side, meaning that insulation manufacturing cost can be reduced. First, the working principle of NFCL cooperation with the DCCB is introduced. Then the main electromagnetic parameter design requirements of the NFCL are analyzed. Their feasibility is verified by electromagnetic circuit simulation, and a prototype is built and tested. Finally, the experimental and simulation results show that NFCL can improve current drop speed effectively.
24 December 2020 in IEEE Transactions on Industrial Electronics
In order to limit the extremely fast rising trend of fault current in a high voltage direct current system, a permanent magnet (PM) biased dc saturated core fault current limiter (DCSFCL) was proposed previously. However, the demagnetization problem of the PM and compromised fault limiting inductance value caused by the inserted PMs are two major issues that need to be solved. In this article, a hybrid-material based fault current limiter (HMFCL) is proposed. First, by means of reconstructing the iron core topology and substituting different soft magnetic materials with their hybrid benefits, the proposed novel HMFCL can present instant change in fault limiting inductance value without threating the safety of the PMs. Then, the Jiles-Atherton hysteresis modeling technique is applied on the HMFCL and its electromagnetic feature is analyzed. The parameters of HMFCL are optimized using genetic algorithm as well. Finally, the effectiveness of the proposed HMFCL is proved by various device and system level simulations as well as a prototype experiment. Results reveal that the proposed HMFCL can limit the fault current by over 80% compared with traditional smoothing reactor.
8 September 2021 in IEEE Transactions on Power Electronics
The traditional saturated core type fault current limiters (TFCLs) cause large energy absorption and high overvoltage in direct current circuit breakers (DCCBs). Energy absorbing FCLs (AFCLs) cause coils to bear the fault current for a long period and the fault energy absorption is slow. In order to solve the problems of TFCLs and AFCLs, a novel fast energy storage dc FCL (EFCL) topology is proposed in this article. The EFCL not only reduces the overvoltage and energy absorption of DCCBs but also quickly stores energy. First, the working principle and topology of the EFCL are proposed. The design requirements of the main electrical and core size parameters are then analyzed. Then, the key electrical parameters are optimized by electromagnetic circuit simulations. The economy is analyzed. Finally, the whole process simulation and FCL comparison simulation are carried out. The feasibility of the EFCL is verified by the comparison of simulation with experiment.