10 September 2018 in IEEE Transactions on Industrial Electronics
This work proposes an observer-based grid-voltage sensorless strategy that allows to implement the synchronization and control of an LCL grid-tied voltage source inverter. By using exclusively the measurement of the current injected to the grid, an observer estimates both fundamental positive- and negative-sequence components of the grid voltage, with a quality (in terms of THD and convergence speed) comparable to that obtained with a classic DSOGI-FLL. The unmeasured LCL filter states are also estimated by the observer, and they are used to implement a full-state feedback control strategy suitable for low resonance frequency LCL filters. The effectiveness of the scheme proposed here is demonstrated by comparison with a DSOGI-FLL and with a controller recently proposed in the literature. Experimental and simulation results that demonstrate the validity and effectiveness of the proposal are presented.
28 June 2019 in IEEE Transactions on Power Electronics
A new structure of a PI current controller implemented in a synchronous $d,q$ reference frame (SRF-PI), for grid-tied voltage inverters, is presented. The controller has a dead beat response for current reference tracking, reaching it in two samples. It also keeps the main feature of the SRF-PI controller: its ability to track without error a positive sequence current reference of fundamental frequency (in the absence of other disturbances). Furthermore, the controller ensures the full decoupling between the currents of axes $d$ and $q$ . The controller is compared, through simulation and experimental results, with one SRF-PI controller recently published in the literature. It is verified that the proposed controller introduces noticeable improvements in both the transient response and in the steady state response to perturbations in the control loop.
20 February 2020 in IEEE Transactions on Industrial Electronics
A strategy for grid impedance estimation is proposed in this work. The strategy is based on the use of an observer suitable to implement the control and synchronization of a VSI with LCL filter, by measuring only the current that the system injects to the grid. The estimation is done based on a modification of the original structure of the observer, together with the implementation of a grid current injection strategy, that allows the observer to adapt in the presence of grid impedance uncertainty. The proposed strategy provides an accurate estimate of the grid impedance inductive and resistive components, suitable for control purposes. The validity and effectiveness of the proposal are demonstrated by simulation and experimental results.
22 May 2023 in IEEE Transactions on Industrial Electronics
A synchronverter (SV) equipped with an output admittance synthesizer is modified to avoid the usual transient instability of grid forming inverters in presence large grid disturbances, keeping the injected currents at safe values. The proposal consists of changing the control objective of the SV: instead of controlling the injected active and reactive powers, the injected active and reactive currents are controlled (as in a grid following inverter). The resulting system [called here current controlled SV, (CCSV)], injects balanced currents, even against asymmetric faults. The CCSV is capable of operating both in island mode and in grid connected mode, and can switch between these modes without prior synchronization. Like the SV, the CCSV does not use a dedicated algorithm for synchronization (such as a phase-locked loop).
1 May 2014 in IET Power Electronics
This study proposes the application of a current controller based on the reduced order generalised integrator (ROGI) to control a three‐phase three‐wire shunt active power filter (SAPF). The ROGI‐based controller has low computational burden and it is suitable for its implementation in low‐cost digital signal processors (DSPs). This controller is also frequency adaptive. This allows it to maintain its high steady‐state performance despite grid frequency variations. Unlike conventional high performance SAPFs this current controller does not require the computation of high quality current references (with low distortion and total harmonic distortion below that recommended by the IEEE Std 519‐1992). Therefore most of the available computational power can be used for compensating the harmonics produced by the load.
6 August 2020 in IEEE Journal of Emerging and Selected Topics in Industrial Electronics
This paper presents a control strategy for three-phase inverters connected to grids through an LCL output filter. For this topology, it is known that when output current and capacitor current are fed back through certain optimal gains, the system is unfailingly unstable for a grid inductance value called "critical". For the critical inductance value, the system's resonance frequency is equal to a sixth of the sampling frequency. In this paper, it is first checked that capacitor voltage positive feedback can stabilize this system. In addition, it is found that there exists a proportional relationship between the common coupling point voltage and the capacitor voltage. Based on this relationship, it is proposed to add grid voltage feedforward instead of capacitor voltage feedback for obtaining a stable system for every grid inductance value, including the critical value. In order to validate our assertion, this control law is tested via simulations and also, experiments on a prototype are included. Simulation and experimental results show the good performance of the proposed scheme.