5 January 2024 in IEEE Transactions on Power Electronics
This article presents an extensive framework focused on the control design, along with stability and performance analyses, of grid-following (GFL) inverters. It aims to ensure their effective operation under both stiff and weak grid conditions. The proposed framework leverages the coupled algebraic structure of the transmission line dynamics in the $dq$ frame to express and then mitigate the effect of coupled dynamics on the GFL inverter's stability and performance. In addition, we simplify the coupled multi-input multi-output (MIMO) closed-loop system of the GFL into two separate single-input single-output (2-SISO) closed loops for easier analysis and control design. We present the stability, robust stability, and performance of the original GFL MIMO closed-loop system through our proposed 2-SISO closed-loop framework. This approach simplifies both the control design and its analysis. Our framework effectively achieves grid synchronization and active damping of filter resonance via feedback control. This eliminates the need for separate phase-locked loop and virtual impedance subsystems. We also utilize the Bode sensitivity integral to define the limits of GFL closed-loop stability margin and performance. These fundamental limits reveal the necessary tradeoffs between various performance goals, including reference tracking, closed-loop bandwidth, robust synchronization, and the ability to withstand grid disturbances. Finally, we demonstrate the merits of our proposed framework through detailed simulations and experiments. These showcase its effectiveness in handling challenging scenarios, such as asymmetric grid faults, low-voltage operation, and the balance between harmonic rejection and resonance suppression.
16 October 2023 in IEEE Access
Seamless recovery and sustained power to critical infrastructures (CIs), after grid failure, is a crucial need arising in disaster scenarios that are increasingly becoming more frequent. Accreditation standards recommend CIs to have emergency power supply system (EPSS) in order to form a local microgrid network with backup resources (generation units/renewable resources) in case of sudden power blackouts of main grid supply. The standards also recommend enhancements such as seamless transition capability during on-grid to off-grid jump and vice versa, efficient and optimal operation while maintaining the standard regulation and power quality limits during power contingencies, and operation with sustenance of reliable power for long periods of time. This article is proposing a comprehensive design of the EPSS for uninterrupted operation of CIs by employing novel techniques, such as 1) mode-dependent droop controlled grid-forming inverters for seamless transition capability; 2) fast-acting optimal net-load management engine for efficient and optimal operations maintaining regulation and power quality limits; 3) optimization-based horizon of viability engine for longer, sustained and viable operation in the aftermath of grid failure as recommended in standards. Two stage validations are conducted using defined test cases while considering various types of contingencies on a 3-ϕ, 60 Hz, 480 V, 450 kVA test system based on a realistic electrical network of a commercial scale medical center. The comprehensive controller-hardware-in-loop and power-hardware-in-the-loop based experiments corroborate the efficacy and robustness of the proposed strategy for EPSS employed in the CI. The mode-dependent droop controller enables seamless transition of the critical infrastructure between the off-grid and the on-grid modes. Inverters operate in the gird-forming mode when the CI is off-grid and also when the CI is on-grid while keeping frequency and voltage regulated between ±0.5 Hz and ±10% of the nominal respectively. The fast-acting net-load management engine maintains the balance in total available generation and the power demand by determining the optimal decisions within 100 ms during various contingencies while regulating the voltage, frequency, and total harmonic distortion (THD) of the system under the strict limit recommended by the grid codes. The horizon of viability optimization engine showcases advantages over conventional scheduling engines with higher utilization of critical loads and maintaining higher energy at the end of an 1-hour experiment.