The corona onset characteristic of bundle conductors is an important limiting factor for the design of UHV AC power lines in high-altitude areas. An experimental study on the corona characteristics of 8 × LGJ630, 6 × LGJ720, 8 × LGJ720 and 10 × LGJ720 bundle conductors commonly used in UHV power lines under dry and wet conductor conditions, as well as artificial moderate and heavy rain conditions, was conducted in Ping’an County, Xining City (elevation 2200 m). By using the tangent line method, the corona onset voltages and onset electric field of four types of conductors at high altitudes are obtained for the first time. In addition, the calculation model of corona onset voltage considering the outer strands’ effect on the electric field and the geometric factor in the corona cage in high altitude areas is established. The comparison of the calculation results and experimental results under dry conditions verifies the model’s correctness. Based on the results, an optimal selection scheme for high altitudes is proposed. The roughness coefficient was also calculated and analysed: the roughness coefficient of bundled conductors was between 0.59 and 0.77, and the roughness coefficient of the wet conductor was between the dry and rainy conditions. Both the experimental data and the calculation model can provide a reference for conductor selection for UHV AC power lines for use in high-altitude areas.
To study the influence of multi-factors, such as long sunshine, sand erosion, and so on, in southern Xinjiang, we selected two kinds of composite insulators for the transmission lines in southern Xinjiang to study the aging characteristics of the umbrella skirt surface. The results of scanning electron microscope (SEM) and X-ray photoelectron spectroscopy (XPS) show that the surface roughness of the umbrella skirt is high and there are a large number of micron inorganic particles. The skirt has the characteristics of low C/O element ratio and high Al element content. The results of thermogravimetric analysis and micro infrared test show that the aging depth of the Myli Line skirt after 19 years of operation is 160~190 µm and that of Yuhe Line 1 after 14 years of operation is greater than 180 µm. The plasma discharge method was used to simulate the corona discharge in the actual operation to accelerate the aging of the surface of the umbrella skirt and the hydrophobic recovery of the umbrella skirt was investigated. The results show that the temperature has a great influence on the surface hydrophobic recovery performance after plasma treatment. These results may provide some theoretical guidance and technical support for the selection, operation, and maintenance of composite insulators in Xinjiang.