A flexible grounding system is a system in which the neutral point of the power supply is grounded via the arc suppression coil in parallel with a low-resistance resistor. When operating normally or a temporary ground fault occurs, the arc suppression coil is used for grounding, whereas the small resistance is switched on when a permanent ground fault occurs. At present, the problem of low protection sensitivity when a high-resistance ground fault occurs in a flexible grounding system has not been solved yet. According to the characteristics of low waveform similarity between the faulty line and the non-faulty line when a single-phase grounding fault occurred, a new faulty line selection method based on a combination of Dynamic Time Warping (DTW) distance and the transient projection method is proposed in this paper. Firstly, the fault transient signal is extracted by a digital filter as a basis for faulty line selection. Secondly, the transient zero-sequence current of each line is projected onto the busbar transient zero-sequence voltage, and the projected DTW distance of each line is calculated. Finally, according to the calculation formula of waveform comprehensive similarity coefficient, the Comprehensive DTW (CDTW) distance is obtained, and the top three CDTW distance values are selected to determine the faulty line. If the maximum value is greater than the sum of the other two CDTW distance values, the line corresponding to the maximum value is judged as the faulty line; otherwise, it is judged as a busbar fault. The simulation results based on MATLAB/Simulink and field data test show that the method can accurately determine the faulty line under diverse fault conditions.
When a single-phase grounding fault occurs in a resonant grounding system, the determination of the fault location remains a significant challenge due to the small fault current and the instability of the grounding arc. In order to solve the problem of low protection sensitivity when a high-resistance grounding fault occurs in a resonant grounding system, this paper proposes a fault location method based on the combination of dynamic time warping (DTW) distance and fuzzy C-means (FCM) clustering. By analyzing the characteristics of the zero-sequence current upstream and downstream of the fault point when a single-phase grounding fault occurs in the resonant grounding system, it is concluded that the waveform similarity on both sides of the fault point is low. DTW distance can be used to measure the similarity of two time series, and has the characteristics of good fault tolerance and synchronization error tolerance. According to the rule that the DTW value of faulty section is much larger than that of nonfaulty sections, FCM clustering is used to classify the DTW value of each section. The membership degree matrix and cluster centers are obtained. In the membership degree matrix, the section corresponding to the data in a class of their own is the faulty section, and all other data correspond to the nonfaulty section; otherwise, it is a fault occurring at the end of the line. The simulation results of MATLAB/Simulink and the field data test show that the method can accurately locate the faulty section.