Connecting photovoltaic micro-installations to a low-voltage network changes the operating conditions of the network. As a result, in certain situations, the permissible operating limits may be periodically exceeded. The risk of exceeding the normal operating conditions of the network depends on multiple factors, including the installed capacity of the photovoltaic sources. In this article, we use a time-series method to determine the annual risks of exceeding the bus voltage limits, the rated current of the lines and transformer, and the acceptable limit of the negative sequence component of bus voltage, as well as the risk of a reverse flow occurring, and the risk of energy losses increasing. We calculate these risks for different levels of penetration of the photovoltaic sources, different divisions of the rated power of the photovoltaic sources between individual phases, and different consumer load profiles. We perform calculations on a CIGRE test network using OpenDSS and statistical meteorological data for the Katowice (Poland) weather station. The results obtained indicate that connecting photovoltaic micro-installations to a low-voltage network has the greatest impact on the risk of reverse flow occurring and the risk of energy losses increasing. In addition, the risk of overvoltage and branch overload increases substantially. The method we present allows one to determine the value of the hosting capacity of a given low-voltage network, ensuring that the assumed risk of exceeding the normal operating conditions of the network is retained.
Photovoltaic (PV) systems are becoming increasingly popular, especially in residential buildings. However, the high penetration of prosumer PV micro-installations can have a negative impact on the operation of distribution networks due to the low self-consumption of the energy produced. One way to mitigate this problem is to use a residential energy storage system (RESS) and load shifting under a demand-side management (DSM) scheme. Energy management systems (EMSs) are used to control the operation of RESSs and to implement DSM. There are two main categories of EMSs: rule-based and optimization-based. Optimization-based EMSs provide better results than rule-based EMSs but can be computationally expensive. This article proposes an optimization-based EMS that is designed specifically for residential buildings. The proposed home energy management system (HEMS) uses a particle swarm optimization method to maximize the prosumer’s financial neutrality, which is calculated based on dynamic energy prices. Simulation-based evaluation using the measurements taken in a building equipped with a PV source, RESS, and shiftable loads shows the improved performance of the proposed HEMS compared to rule-based RESS control. The results show that the designed HEMS increases self-consumption, thus reducing the impact of the prosumer’s PV micro-installations on the distribution grid.
8 February 2026 in Energy Conversion and Management
Artykuł stanowi opis propozycji zastosowania skanera wykorzystującego światło strukturalne w celu identyfikacji wad detali poddawanych obróbce. Artykuł stanowi część prac związanych z opracowaniem linii do automatycznej identyfikacji wad na elementach obrabianych. W artykule dokonano uzasadnienia wyboru metody skanowania oraz wyniki pomiarów przy użyciu skanerów światła strukturalnego określające możliwości wykorzystania ich w wizyjnej detekcji wad.
W artykule przedstawiono wpływ prosumenckich instalacji fotowoltaicznych na pracę sieci rozdzielczej niskiego napięcia. Symulacje pracy sieci zostały przeprowadzone w programie OpenDSS, z wykorzystaniem modelu sieci testowej CIGRE. Na podstawie uzyskanych wyników określono wpływ warunków atmosferycznych na ryzyko przekroczenia normalnych warunków pracy sieci. Ponadto określony został maksymalny stopień nasycenia sieci CIGRE źródłami PV, który nie powodował zaburzeń w pracy tej sieci