Csaba Beres

Mr. Csaba Beres


Research Focus & Metrics

Academic Career Length

5Years (2022-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
24 December 2022 in Energies
Verified
Journal Article
Open access
PDF file
AKAttila Kostyak
Attila Kostyak
CBCsaba Beres
Csaba Beres
SSSzabolcs Szekeres
Szabolcs Szekeres
CICsáky Imre
Csáky Imre
In this article, energy optimization of the cooling system of IKEA Budaörs is carried out. The cooling system is served by a centrifugal water chiller and includes a large-volume cooling buffer tank. The facility operates the hydraulic system of the buffer storage tank only during the transitional period. The main goal is to reduce energy consumption by changing the operating strategy of the existing system. To test the operating strategies, the operation and the thermal load of the shopping center during the summer season had to be simulated to find the best operation strategy. A hybrid method (real data and calculated values) was used in the simulation. The three operating scenarios examined show that the annual energy consumption and the number of operating hours of the chiller can be reduced by using the buffer tank with the right strategy. In the examined scenarios, a 30% energy improvement was achieved. The possibility of using a buffer tank is significantly limited by the fact that the heat exchangers were sized for low forward water temperatures. By re-sizing the heat exchangers, the utilization of the buffer tank could be considerably improved in conditions close to peak heat load.