Medium-deep borehole heat exchangers (MBHEs) have received increasing attention with respect to building heating. To avoid the thermal interference of adjacent MBHEs, the temperature distribution characteristics of medium-deep rock soil were investigated in this work. The evolution of the maximum rock-soil thermal affected radius (MTAR) over a full lifecycle was analyzed. The results showed that the rock-soil thermal affected area (RTAA) continuously expanded in both the radial and vertical directions when the MBHE continuously extracted geothermal energy during a heating season. The factors of the thermal extraction load, fluid velocity, geothermal gradient, and pipe length, impacted the RTAA in the vertical direction, while rock-soil thermal conductivity affected the RTAA in both the radial and vertical directions. Furthermore, the thermal affected radius (TAR) in deeper formations was larger, reaching even 96 m, such that thermal interference between adjacent MBHEs was more likely to occur. The MTAR in shallow formations was limited to 20 m. Consequently, a new layout form, achieved by inclining the borehole, was proposed to increase the distance between adjacent MBHEs in deep formations. The recommended incline angle was equal to or larger than four times the TAR angle. This work provides a scientific reference for promoting the application of multiple MBHE arrays.
An accurate prediction for deep-buried ground heat exchangers (DBGHEs) is the premise for efficient utilization of geothermal energy. Due to the complexity of the geological composition spanning thousands of meters, the configuration of boundary conditions plays a critical role in evaluating DBGHE thermal performance. This paper proposed a three-dimensional model of full-scale DBGHE involving both conductive and convective heat transfer in aquifuge and aquifer layers. The constant inlet temperature and constant heating power boundaries in the DBGHE domain, and the surface–bottom temperature and heat flux boundaries in the rock-soil domain were examined. It was found that the differences in the performance prediction caused by different DBGHE boundary conditions were closely related to the system’s operating time. The relative differences in heat extraction amount and average borehole temperature of 2000 m DBGHE caused by the two inlet boundaries on the 30th day were, respectively, 19.5% and 18.3%, while these differences on the 120th day were decreased to 8.4% and 9.9%, respectively. It was found that the constant inlet temperature boundary was more appropriate than the constant heating power condition for estimating aquifer effects on the performance of DBGHE. For the rock-soil domain, the results showed that the heat extraction amount of DBGHE under the heat flux boundary was 12.6%–13.6% higher than that under the surface–bottom temperature boundary. Particularly, when considering the velocity change of groundwater in the aquifer, the relative difference in heat extraction amount increments caused by the two types of rock-soil boundaries can reach 26.6% on the 120th day. It was also found that the thermal influence radius at the end of a heating season was hardly affected by either the DBGHE inlet or rock-soil domain boundary conditions.