This paper presents a theoretical and experimental study on the ampacity of the prefabricated straight-through joint of a 110 kV high voltage cable. Thermal modelling revealed that the critical spot limiting the ampacity of this type of cable joint is located on its crosslinked polyethylene (XLPE) insulation section. The axial distribution of the thermal field in this type of cable joint was also determined. An algorithm for assessing ampacity in this type of cable joint was developed. Experiments were conducted on a real cable system with a prefabricated straight-through joint under different loading conditions. The experiments show a good agreement with the thermal modelling results.
Ground wire breakage accidents can destroy the stable operation of overhead lines. The excessive temperature increase arising from the contact resistance between the ground wire and armor rod in the contact terminal is one of the main reasons causing the breakage of ground wires. Therefore, it is necessary to calculate the equivalent resistance for ground wires twined with armor rods in contact terminals. According to the actual distribution characteristics of the contact points in the contact terminal, a three-dimensional electromagnetic field simulation model of the contact terminal was established. Based on the model, the current distribution in the contact terminal was obtained. Subsequently, the equivalent resistance of a ground wire twined with the armor rod in the contact terminal was calculated. The effects of the factors influencing the equivalent resistance were also discussed. The corresponding verification experiments were conducted on a real ground wire on a contact terminal. The measurement results of the equivalent resistance for the armor rod segment showed good agreement with the electromagnetic modeling results.
With the increase in electricity demand, the ampacity calculation based on the dynamic thermal rating (DTR) technology is increasingly significant for assessing and improving the power transfer capacity of the existing overhead conductors. However, the DTR models now available present some inadequacies in measurement techniques related to wind speed. Therefore, it is essential to propose a new model instead of wind speed measuring in DTR technology. In this paper, the influence analysis of various weather parameters on the conductor ampacity is carried out by using the real weather data. Based on the analysis, it is confirmed that the impact of wind speed is significant, especially in the case of the low wind speed. Moreover, an equivalent heat transfer (EHT) model for DTR technology is proposed instead of wind speed measuring. For this EHT model, the calculation of conductor ampacity is realized through investigating the correlation of heat losses between the heating aluminum (Al) ball and conductor. Finally, combined with the finite element method (FEM), the EHT model proposed in this paper is verified by the Institute of Electrical and Electronic Engineers (IEEE) standard. The results indicate that the error of the EHT model is less than 6% when employing the steady thermal behavior of the Al ball to calculate the ampacity. The EHT model is useful in the real-time thermal rating of overhead conductors. It can increase the utilization of overhead conductors while also avoiding the limitation of the existing measurement techniques related to wind speed.