Commutation failure immunity index (CFII) is a useful indicator to quantify the immunity level to commutation failures in line commutated converter‐based multi‐infeed HVDC systems. Instead of using simulation tools which inevitably lead to heavy workload and long computation time, the analytical expressions of ‘local CFII’ (LCFII) and ‘concurrent CFII’ (CCFII) are derived based on the minimum extinction angle criteria. Using these expressions, the impact of the system parameters on commutation failure immunity levels in the inverter side can be determined quickly and effectively. Moreover, the derived analytical expressions will make the parametric sensitivity analysis more comprehensive and complete compared to the traditional simulation‐based methods. Furthermore, in order to give an insight into how inter‐inverter interactions influence the concurrent commutation failure behaviours, an improved index ‘weak coupling multi‐infeed interaction factor’ (WCMIIF) is proposed. The validity and accuracy of the proposed index and analytical expressions are verified by the simulated results based on a dual‐infeed HVDC system in PSCAD/EMTDC, which indicate that LCFII has an approximately linear correlation with the local effective short‐circuit ratio (ESCR) of the faulted ac system, and that with the WCMIIF unchanged, CCFII has an approximately linear correlation with the local ESCR and an inverse correlation with the multi‐infeed interaction factor.
23 September 2019 in IEEE Transactions on Power Electronics
Earlier approaches for commutation failure (CF) risk areas identification in multi-infeed LCC-HVDC systems include the simulation-based and analytical types. However, the former and latter will cause the low computational efficiency and inaccurate result respectively. Thus, this paper firstly clarifies CF performances caused by voltage depression and distortion in multi-infeed LCC-HVDC systems. Secondly, an ac-dc interaction factor (ADIF) index along with its analytical calculation method is proposed to quantify the voltage interaction between arbitrary ac line location and inverter bus. The ADIF is then used to develop a critical ADIF (CADIF) index for identifying the voltage depression induced CF. Thirdly, a distortion ADIF (DADIF) index along with its mathematical expression is developed for identifying the voltage distortion induced CF. Fourthly, combining the voltage depression and distortion induced CF identification methods, CF correlation regions where ac faults can induce CF in inverters are introduced to develop the proposed approach. Compared to earlier simulation-based approaches, the proposed approach is more efficient without recourse to simulations; Compared to earlier analytical approaches ignoring ac lines faults and the voltage distortion induced CF, the proposed approach is more accurate with these factors comprehensively considered. Finally, case study on an 8-infeed LCC-HVDC system validates the proposed approach.
28 May 2020 in IEEE Transactions on Power Delivery
To deal with the high-resistance fault identification problem in multi-terminal VSC-HVDC, this paper proposes a high fault-resistance tolerable traveling wave protection. First, the non-unified characteristic of traveling wave front between internal and external faults is revealed, which makes the high-resistance fault identification difficult. Then, the traveling wave propagation regarding the reflection and refraction process at the remote end is investigated for the difference, and the distinctive current reduction phenomenon during the interval of two incident traveling waves under internal fault with resistance is discovered. Moreover, the current reduction phenomenon would become more significant with the increase of fault resistance. Based on this phenomenon, the high fault-resistance tolerable traveling wave protection is proposed, which could identify the high-resistance fault accurately with single-end measurement and is insensitive to fault resistance. The feasibility and robustness of the proposed protection are validated in a four-terminal VSC-HVDC.
13 July 2020 in IEEE Transactions on Power Systems
Voltage harmonics are very likely to cause commutation failure (CF) in multi-infeed LCC-HVDC systems. However, this has not been sufficiently considered in earlier CF detection methods and control strategies. In this paper, by incorporating the voltage harmonics into the inverter quasi-steady-state model, an extinction angle predictive algorithm is firstly presented to propose the enhanced CF predictive detection method. Compared to earlier methods, the enhanced method can detect both local and concurrent CFs more accurately. Moreover, the enhanced method is then used as the starting unit of the enhanced CF predictive control strategy to enable its effective activation. To develop the enhanced strategy, a firing angle order predictive algorithm is introduced using the inverter quasi-steady-state model with the voltage harmonics considered. Compared to earlier strategies, the enhanced strategy can mitigate both local and concurrent CFs more effectively. Furthermore, the response speed of the enhanced method and strategy is evaluated by comparing CF characteristics and signal process delay. It is shown that since the timescales of the voltage harmonics induced CFs are longer than signal process delay, the response speed is fast enough to ensure their practicality. Finally, simulation results based on a dual-infeed LCC-HVDC system validate the enhanced method and strategy.
17 December 2019 in IEEE Transactions on Power Delivery
The multi infeed interaction factor (MIIF) index was introduced by CIGRE as a measure of inter-inverter interactions in multi-infeed HVDC systems, which include only line-commutated converter based HVDC (LCC-HVDC) links. The MIIF is although valid among LCCs in hybrid multi-infeed HVDC systems, but not among voltage-source converters (VSCs) as well as between LCC and VSC when the VSC operates under the constant ac voltage control mode. In this paper, a multi-infeed voltage interaction factor (MVIF) index is firstly proposed as the quantitative measure of inter-inverter interactions in hybrid multi-infeed HVDC systems. Compared to the MIIF, the MVIF is unified since it is applicable regardless of inverter types and control modes. Moreover, the quasi-steady-state power-flow model of hybrid multi-infeed HVDC systems is utilized as the mathematical framework to develop the analytical calculation method of the MVIF. This lends a theoretical basis for the efficient evaluation of inter-inverter interactions. Furthermore, the parametric dependence of the MVIF is analyzed to provide an exhaustive perspective of inter-inverter interactions. This offers a useful tool to aid planning and operation of hybrid multi-infeed HVDC systems. Finally, dynamic simulations conducted on the PSCAD/EMTDC program validate the MVIF and its analytical calculation method.
10 September 2019 in IEEE Transactions on Sustainable Energy
Leveraging multiple heterogeneous measurements to predict wind power has long been a challenging task in the electrical community. In this paper, a deep architecture incorporated with multitask learning and multimodal learning for wind power prediction, termed predictive stacked autoencoder (PSAE), is presented. PSAE is a unified framework integrating multiple stacked autoencoders (SAEs), one feature fusion layer, and one prediction terminal layer, which expands the architecture from two spatial dimensions, including the depth and width, compared to conventional prediction models. Initially, the SAEs at the bottom of PSAE extracted features from multiple kinds of measurements respectively. Following, the feature fusion layer encodes the high-order features extracted by different SAEs into a unified feature that is more informative and representative for wind power prediction. Finally, the prediction terminal layer functions as a regression machine which generates the predicted targets based on the fusion features. Trained in an end-to-end (E2E) manner, PSAE is capable of learning heterogeneous features jointly and achieving the prediction task of sequence-to-sequence (S2S). Experiments for multi-step short-term predictions are conducted on real-world data, and the results demonstrate the superiority of PSAE to prior methods.