Small data centers can be integrated into the energy systems of commercial and tertiary buildings to capture waste heat generated by servers, mitigate environmental impacts and enhance energy efficiency. This study introduces a novel methodology for maximizing waste heat capture from the cooling coils by optimizing workload distribution in an edge data center consisting of air-cooled servers. The maximization of outlet temperatures algorithm (MOTA) was developed using a validated fast thermal evaluation approach. Experimental studies were conducted to characterize parameters of the cooling system such as air and water flow rates and effectiveness of the coil. A multi-region conjugate heat transfer (CHT) numerical model was developed to demonstrate feasibility of the proposed approach. Heat transfer through the cooling coil was numerically modeled using the effectiveness-NTU method. Good agreement was achieved between the simulated and measured water temperatures at the outlet of the cooling coil. Numerical simulations conducted using the validated CHT model show that the MOTA can improve heat recovery by up to 17.1% under various IT loads. Furthermore, optimizing the water flow rate can reduce the cooling load by up to 53.2%. These combined results highlight the potential of the proposed algorithm for energy-efficient management of data centers. Computational cost and real-world applicability of the proposed algorithm were discussed in detail.
This study represents the development and optimization of a micro-baffle design to enhance heat transfer in film boiling. Numerical simulations are performed using an open-source computational fluid dynamics (CFD) model, which incorporates the Lee model for momentum source associated with the phase change, and the Volume of Fluid (VOF) method to capture bubble dynamics. A comparison of the numerical results with the previous numerical and experimental data confirmed the validity of the numerical model. The influence of key design parameters was systematically investigated. The results revealed that a vertical baffle provided the maximum performance. The optimal baffle design achieved a 57.4% improvement in the Nusselt number and a 66.4% increase in critical heat flux (CHF). Furthermore, the proposed design facilitated continuous bubble formation, even with a reduced temperature difference between the heated surface and the subcooled liquid, which is crucial for energy-efficient thermal management in engineering systems. Ultimately, this study demonstrates the potential of micro-baffle designs in controlling bubble dynamics and improving heat transfer in film boiling, thereby aiding the design of efficient thermal systems.