Modeling IT equipment is of critical importance for the simulations of flow and thermal structures in air cooled data centers. Turbulent flow undergoes a significant pressure drop through the server due to the energy losses originating from the internal components. Therefore, there is an urgent need to develop a fast and an accurate method for the calculation of pressure losses inside server components for data center applications. In this study, high resolution numerical simulations were performed on an OCP (Open Compute Project) server under various inlet flow rates for inactive and active conditions. Meanwhile, one key challenge of modeling complete geometry of the server results from using an intense mesh even for a single server. To address this challenge, the server was modeled as a porous zone to mimic inertia and viscous resistance in a realistic way. Comparison of the results of porous and complete models showed that the proposed model could calculate pressure drop accurately even when the number of cells in the server was reduced to 0.3% of the complete model. Porosity coefficients were determined from the numerical simulations conducted in a broad range of air discharge for both active and inactive conditions. Errors in the calculation of pressure drop may result in a significant deviation in the prediction of the temperature rise over the server. Thus, the present model can effectively be used for the fast and accurate prediction of pressure drop inside a server component rather than solving internal flow on an intense mesh, while simulating airflow inside an air-cooled data center, which is crucial for the design safety of data centers. Finally, calculated porosity coefficients can be used for the prediction of the pressure drop in a server, while designing data centers based on numerical simulations.
In this study, an open-source computational fluid dynamics (CFD) model was developed based on OpenFOAM libraries for the accurate and robust simulation of thermal distribution in a data center. Two boundary conditions were developed for the temperature field in the black-box modeling of server components. The numerical model was first validated by comparing numerical results with the experimental measurements for three benchmark problems in the field of thermal engineering. Then, thermal distribution in an open-aisle data center was simulated using the proposed numerical model and results were compared with the experimental measurements. The consistency between numerical results and previous experimental measurements indicates that the present numerical model can be reliably used for the efficiency assessment of air-cooled data centers. Efficiency of the data center can be evaluated with respect to four metrics in the proposed numerical model. In addition to the determination of the overall efficiency, distribution of the efficiency can be monitored over the racks to capture thermal zones where the efficiency decreases due to the recirculation effects and cold air by-pass.
Liquid-cooled servers can be deployed to reduce the energy consumption and environmental footprint of hybrid-cooled data centers. A computational fluid dynamics (CFD) model can bring extremely useful insights and results for thermal simulations of air- and liquid-cooled servers in a single environment. In this study, a conjugate heat transfer (CHT) numerical model is developed and validated with experimental data to simulate heat transfer from the CPU to the air and cold plate considering the effect of thermal paste. The cooling performance of an in-house developed cold plate design is thoroughly investigated via the validated CHT model. A dataset containing one hundred samples of various flow, thermal and workload conditions was generated using the Latin hypercube sampling (LHS) method, which was further utilized in the series of CHT simulations. Finally, a novel empirical equation is proposed for the prediction of heat transfer from the CPU to the air. The accuracy of the proposed equation is confirmed by comparing estimated and simulated results for a test dataset. A thermal analysis of a rack containing air and liquid-cooled servers is performed using the presented approach. The simulation results reveal that the proposed compact model can be used reliably for the thermal simulation of a hybrid-cooled data center.
This article provides experimental and numerical data for the flow and thermal distributions inside an air-cooled data center. The experimental data contains the exhaust temperature profile obtained from an experimental campaign and the numerical data contains OpenFOAM and script files for the simulation of the thermal structure based on the experimental study. Experimental measurements were conducted using temperature sensors located at the rear of the rack under a working scenario of 2 kW. Publically available experimental data, numerical model and results can be used for the validation of numerical models under the thermal scenario given in the present study. Flow and thermal structures inside the data center are exhibited using the validated numerical model.
This study represents the development and optimization of a micro-baffle design to enhance heat transfer in film boiling. Numerical simulations are performed using an open-source computational fluid dynamics (CFD) model, which incorporates the Lee model for momentum source associated with the phase change, and the Volume of Fluid (VOF) method to capture bubble dynamics. A comparison of the numerical results with the previous numerical and experimental data confirmed the validity of the numerical model. The influence of key design parameters was systematically investigated. The results revealed that a vertical baffle provided the maximum performance. The optimal baffle design achieved a 57.4% improvement in the Nusselt number and a 66.4% increase in critical heat flux (CHF). Furthermore, the proposed design facilitated continuous bubble formation, even with a reduced temperature difference between the heated surface and the subcooled liquid, which is crucial for energy-efficient thermal management in engineering systems. Ultimately, this study demonstrates the potential of micro-baffle designs in controlling bubble dynamics and improving heat transfer in film boiling, thereby aiding the design of efficient thermal systems.