Xincui Tian

Xincui Tian


Research Focus & Metrics

Academic Career Length

7Years (2020-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
27 February 2020 in IEEE Transactions on Power Delivery
Verified
Journal Article
Closed access
HSHongchun Shu
Hongchun Shu
XLXuhan Liu
Xuhan Liu
XTXincui Tian
Xincui Tian
In terms of single-ended fault location for hybrid distribution lines, the most significant challenge is in the identification of the fault section and reflected wave from the fault point. Based on this, in this paper we introduce a new fault- section-location identification scheme for hybrid distribution feeders with only single-ended measurement. With the prior morphological spectrum-based fault-section identification technique, a location function is then built by the forward and backward traveling-wave components to describe the characteristic distribution of the traveling wave along the line. With the application of two-dimensional information (which is about time and space) of the traveling wave, it is simpler to locate the actual point of failure. The proposed scheme is investigated under different fault locations, fault resistances, sampling rates, fault inception angles, fault types, etc. The influences of immeasurable voltage traveling wave, adjacent sound lines, and measurable joint point are also investigated. Simulation results confirm the feasibility of the fault-location scheme for all test cases.

1 November 2023 in IEEE Transactions on Industrial Electronics
Verified
Journal Article
Closed access
HSHongchun Shu
Hongchun Shu
YTYusong Tian
Yusong Tian
SLShunguang Lei
Shunguang Lei
GWGuangxue Wang
Guangxue Wang
XTXincui Tian
Xincui Tian
YTYutao Tang
Yutao Tang
The environment of ultrahigh-voltage long-distance hybrid cascading overhead dc transmission lines is complex, and the line fault probability is high. The transmission time of the conventional pilot protection via optical fiber communication is long, causing delays in the implementation of protective actions and seriously affecting the protection scheme's responsiveness. This article, an accelerated backup protection suitable for long-distance dc transmission lines is proposed. Using the Chebyshev digital filter to extract the high-frequency components of the fault voltage, the protection scheme uses the ratio of the components on both sides of the electrical boundary of the dc transmission line to formulate a directional element. Based on the directional elements on both sides of the line, a blocking-type pilot directional protection is established. Experiments show that the backup protection scheme can reduce the protection time compared with the traditional pilot protection, and also has the ability of accurate fault pole selection. The protection principle and method have strong robustness to transition resistance and noise.

28 October 2025 in IEEE Transactions on Power Delivery
Verified
Journal Article
Closed access
XTXincui Tian
Xincui Tian
TZTuoji Zhu
Tuoji Zhu
JSJieshan Shan
Jieshan Shan
YZYining Zhang
Yining Zhang
HSHongchun Shu
Hongchun Shu
Due to significant attenuation, small abrupt changes, and high noise interference present in fault traveling waves obtained from long-distance transmission lines under actual field conditions, fault location algorithms based on traditional mother wavelets (e.g., the Morlet one) have failed to reliably and accurately detect secondary fault traveling waves. To address this issue, a new mother wavelet is developed inferred from fault-morphology features in actual field conditions by satisfying the necessary and sufficient criteria for wavelet functions. The article also analyzes the traveling wave characteristics of faults in both the positive and negative long-distance transmission lines from the perspective of electromagnetic coupling, demonstrating that the high-frequency components contained in both lines are essentially identical. The performance of the proposed algorithm has been verified using actual field data and compared with the results obtained using the conventional Morlet mother wavelet.

25 October 2024 in Electronics
Verified
Journal Article
Open access
PDF file
HLHao Li
Hao Li
ZZZicong Zhang
Zicong Zhang
BDBinghou Ding
Binghou Ding
YBYaoxing Bai
Yaoxing Bai
YZYong Zheng
Yong Zheng
XTXincui Tian
Xincui Tian
The aim of this study was to manufacture alternative Siemens DC measurement system equipment to solve the problems of increased failure rates of foreign DC measurement equipment and the stopped production of key parts. In this paper, the overall structure and common faults of the Siemens DC measurement system are introduced, the difference between TDM signal frame structure and FT3 frame structure is detailed, and the related functional structure, chip type, and function of the Siemens distal module and merging unit (including laser function) are studied. The remote module, merging unit (including laser function), and related hardware design and software design to replace the Siemens DC measurement system were developed, and the test environment and control protection, fault recording wave for communication, and other functional tests were built. The test results show that the domestic remote module, merging unit (laser function), and other technologies communicate normally with the existing Siemens and the domestic mainstream manufacturers, and the accuracy meets the requirements of the 0.2 level.


17 April 2026 in IEEE Transactions on Industrial Electronics
Verified
Journal Article
Closed access
JSJieshan Shan
Jieshan Shan
XWXinglong Wang
Xinglong Wang
XTXincui Tian
Xincui Tian
JYJinyun Yu
Jinyun Yu
HSHongchun Shu
Hongchun Shu
To enhance the protection reliability of high-voltage direct current (HVDC) transmission lines under high-impedance grounding and complex conditions, this article proposes a novel density-based adaptive protection scheme that integrates statistical learning with proactive control strategies. The method first employs principal component analysis to reduce the dimensionality and visualize the projection of transient fault features, revealing their continuous distribution patterns in the feature space. Subsequently, kernel density estimation is introduced to probabilistically model the projection distribution of fault samples, thereby delineating the internal fault zone, external fault zone, and the fuzzy transition region between them. Based on the relative position of real-time fault characteristics in this probability space, the protection system adaptively triggers a hierarchical action strategy, including millisecond-level fast isolation, cooperative discrimination using information from the remote terminal, or protection blocking. The proposed method is validated through electromagnetic transient simulation and 31 field fault cases, demonstrating the following performance metrics: protection accuracy of 96.8% (14.5% points higher than traditional traveling-wave protection), average response time of 29 ms (meeting the speed requirements of HVDC line protection), and maloperation rate of 1.9%. Moreover, the scheme effectively identifies faults with transition resistance up to 300 $\boldsymbol{\Omega}$ and maintains stable performance under noise interference, achieving a desirable balance among reliability, speed, and adaptability.