Traveling-wave-based fault location methods are widely used for modern power systems owing to their high accuracy on two-terminal lines. However, they perform poorly on hybrid multi-terminal lines. Many traveling-wave-based methods have been developed recently to solve this problem, but they have high computational burdens and complex fault location procedures. To tackle this challenge, a new fault location method is presented in this paper. First, to ensure that the implementation of the proposed method is not affected by different line parameters, a normalization algorithm is used for hybrid multi-terminal lines, which consist of overhead lines and cables. To reduce the complexity, a novel fault section identification method that depends only on the first three arrival times is applied to separate a three-terminal fault section from the multi-terminal lines. Consequently, the fault can be located using a corresponding two-terminal fault location method in this fault section. To verify its effectiveness, fault case studies and performance evaluations are performed in the PSCAD and MATLAB/Simulink environment. The simulation results reveal that the proposed method can correctly identify the fault section and accurately locate the faults, which is simple and suitable for hybrid multi-terminal lines.
Traveling-wave-based methods perform poorly for the fault location of multi-terminal lines as a result of the limitation introduced by being a highly branched structure. The requirement for multi-terminal time synchronization is also a drawback and needs to be improved. In this paper, an effective fault location method for use on multi-terminal lines is proposed, and it does not require the data from each terminal to be synchronized. The method is based on the arrival time differences in the ground and aerial mode waves detected at each terminal. First, fault section identification rules for a three-terminal line are proposed. Then, a multi-terminal topological structure in this paper will be deemed as one consisting of multiple three-terminal lines. Thus, a whole scheme to identify any fault section in a multi-terminal line is presented. Consequently, the fault distance is calculated using the fault distance ratios in the corresponding fault section. The advantage of the proposed scheme is that complete coverage of multi-terminal lines fault location can still be achieved once some synchronized devices are out of operation. To evaluate the performance of the proposed method, many fault cases under different conditions are implemented. The simulation results show that the proposed method can identify the fault section correctly and locate the fault more accurately and reliably than existing methods.