In recent years, new fire loads dominated by power banks have caused multiple fire incidents in transportation hubs, posing severe challenges to fire safety. This study uses experimental testing and machine learning regression analysis to explore the heat release rate (HRR) characteristics and influencing factors of box-type power banks under fire conditions. A 1 MW calorimeter was used to conduct four sets of experiments involving a total of 15 box-type power banks, measuring the HRR and analyzing its correlation with oxygen consumption, carbon dioxide generation, smoke temperature, and the fire growth rate. Based on the experimental data, HRR prediction models were constructed using decision tree regression (DT), K-nearest neighbor regression (KNN), and linear regression (LR). The results indicate that the DT model performs best in HRR prediction (MAE = 0.4889, MSE = 0.7414, RMSE = 0.8571, R2 = 0.9991), effectively capturing the nonlinear variation patterns in the HRR. The correlation analysis and regression analysis conducted in this study provide crucial data support for fire combustion characteristics research, fire risk assessment, and fire safety optimization. Furthermore, the findings provide crucial data support for research on fire combustion characteristics and data-driven fire risk assessment, which may serve as a foundation for future AI-based real-time fire detection applications.
Metropolitan city express line tunnels are fully enclosed and often span long distances between stations, allowing multiple trains within a single interval. Traditional segmented ventilation ensures only one train per section, but ultra-long tunnels with shaftless designs introduce new challenges under fire conditions. This study investigates smoke behavior in an ultra-long inter-district tunnel during multi-train blockage scenarios. A numerical model evaluates the effects of train spacing, fire source location, and receding spacing on smoke back-layering, temperature distribution, and flow velocity. Results indicate that when train spacing exceeds 200 m and longitudinal wind speed is above 1.2 m/s, the impact of train spacing on smoke back-layering becomes negligible. Larger train spacing increases back-layering under constant wind speed, while higher wind speeds reduce it. Fire source location and evacuation spacing affect the extent and pattern of smoke spread and high-temperature zones, especially under reverse ventilation conditions. These findings provide quantitative insights into fire-induced smoke dynamics in ultra-long tunnels, offering theoretical support for optimizing ventilation control and evacuation strategies in urban express systems.
In order to provide fire-scene parameters for fire protection design and data support for fire safety management of waiting halls in high-speed railway stations, this study systematically investigated the combustion characteristics of single, two, and three massage chairs using an industrial calorimeter. The results showed the following: The change in heat release rate in the growth stage of the massage chairs’ combustion tests was consistent with the t2 fast fire (with a growth coefficient of 0.04689). The maximum HRR was 1.2 MW for the single-massage-chair combustion test, 2.5 MW for the two-massage-chairs combustion test, and 3.5 MW for the three-massage-chairs combustion test. In the full-scale massage chairs combustion test, setting a 6.0 m fire isolation zone could effectively serve the functions of fire prevention and heat insulation. Considering a certain safety margin, and with a safety factor of 1.5 adopted, it is recommended that a fire isolation zone with a width of 9.0 m be used in the waiting halls of high-speed railway stations, which provides a direct, actionable design basis for engineering practice.
This study aims to provide a reference for the fire protection design and fire emergency response strategies for fuel islands in high-speed railway stations and other transportation buildings. By using an industrial calorimeter, this paper analyzes the combustion characteristics of a fuel island. For the fuel island setup in this test, the fuel island fire development cycle was relatively long, and the maximum fire source heat release rate reached 4615 kW. Before the fire source heat release rate reaches the maximum peak, the HRR curve slowly fluctuates and grows within the first 260 s after ignition. Within the time range of 260 s to 440 s, the fire growth rate resembled that of a t2 medium-speed fire, and within the time range of 400 s to 619 s, it more closely aligned with a t2 fast fire. It is generally suggested that the growth curve of t2 fast fire could be used for the numerical simulation of fuel island fires. The 1 h fire separation method adopted in this paper demonstrated a good fire barrier effect throughout the combustion process.