Point-type smoke fire detectors have become one of the most commonly used technical means in the fire detection systems of ancient buildings. However, in practical applications, their performance is easily affected by special environmental interference factors. Therefore, in this study, a full-scale experimental scene of an ancient building with a typical flush gable roof structure was taken as the research object, and the differential influence laws of three typical interference sources, namely wind speed, water vapor, and incense burning, on the response times of point-type smoke detectors were quantified. Moreover, the prediction models of the alarm time of the detectors under the three interference conditions were established. The results indicate the following: (1) Within the range of experimental conditions, there is a quantitative relationship between the detector response delay and the type of interference source: the delay time shows a nonlinear positive correlation with the wind speed/water vapor interference gradient, while it exhibits a threshold unimodal change characteristic with the burning incense interference gradient; (2) under interference conditions, the detector response delay varies depending on the type of fire source: the detector has the best detection stability for smoldering smoke from a smoke cake, while it has the lowest detection sensitivity for smoldering smoke from a cotton rope. Moreover, the influence of wind speed interference is weaker than that of water vapor or smoke from burning incense, and the difference is the greatest in the wood block smoldering condition. (3) Construct a detector alarm time prediction model under three types of interference conditions, where the wind speed, water vapor, and burning incense interference conditions conform to third-order polynomial functions, Sigmoid functions, and fourth-order polynomial functions, respectively.
Arc fault detection is a key technology for preventing electrical fires. However, existing research has primarily focused on series connections, with insufficient attention paid to parallel load conditions, which are prevalent in real-world residential electricity usage. In accordance with the UL 1699 and IEC 62606 standards, this study established an experimental platform for arc faults, incorporating seven single loads (categorized into four types) and nine multi-load combinations. A systematic analysis of the differences in time–frequency characteristics under different connection modes was conducted. Time-domain and frequency-domain analyses revealed that under parallel connection the dispersion of arc fault time-domain characteristics decreases by more than 50% and the fundamental frequency component increases significantly. For parallel multi-load scenarios, the fundamental component of resistive combinations can reach 90%, while the frequency variance of inductive combinations can be as high as 400,000. By elucidating the time–frequency domain characteristics of parallel arc faults, this study proposes an optimized feature parameter analysis scheme for electrical fire monitoring systems. Based on this, this paper proposes an arc fault detection method using the Dual-Channel Convolutional Neural Network (DCNN). The method achieves 97.09% recognition accuracy for arc faults with different connection modes. Comparative experiments with other models and ablation studies show that the model attains 98.52% detection accuracy, verifying the effectiveness of the proposed method. This approach can significantly improve the accuracy of arc fault detection in multi-load environments, thereby enabling early warning of electrical circuit faults and potential fire hazards.