Traditional monitoring methods cannot obtain the overall thermal information for power transformers. To solve this problem, a distributed fiber optic sensor (DFOS) was creatively applied inside an operating 35 kV power transformer by highly integrating with the electromagnetic wires. Then, the transformer prototype with totally global sensing capability was successfully developed and it was qualified for power grid application through the strict ex-factory tests. The as designed optical fiber sensor works stably all the time with a temperature accuracy of ±0.2 °C and spatial positioning accuracy of 0.8 m. Based on the obtained internal temperature distribution, Gaussian convolution was further applied for the signal processing and hereby, the hotspots for all the windings and iron cores could be accurately traced. The hottest points were located at 89.1% (55 °C) of the high voltage winding height and 89.7% (77.5 °C) of the low voltage winding height. The actual precise hotspot location corrected the traditional cognition on the transformer windings and it would serve as an essential reference for the manufactures. This new nondestructive internal sensing and condition monitoring method also exhibits a promising future for the DFOS applying in the high-voltage electrical apparatus industry.
With the development of fiber optic sensing technology, optical fiber sensors have been widely used in online monitoring of power transformers. To investigate the influence of aging fiber sheaths on transformer oil, two kinds of special optical fibers with thermoplastic polyester elastomer (TPEE) and poly tetra fluoroethylene (PTFE) as sheaths underwent thermally accelerated aging in transformer oil at 130 °C. The volume resistivity, dielectric dissipation factor (DDF), and breakdown voltage of the oil were measured to indicate insulation strength. The water content and acid value of the oil were measured and fitted to predict the aging tends. The thermal aging characteristics of the oil were quantitatively compared and results showed two kinds of optical fibers could exacerbate all the physical and chemical parameters of oil, and the TPEE sheath had a more significant impact on the oil. The reasons contributing to such phenomenon were analyzed using Fourier transform infrared spectroscopy (FTIR) and scanning electron microscopy (SEM). Both TPEE and PTFE were depolymerized in high-temperature transformer oils, producing water and small molecule hydrocarbon groups. The accumulation of small hydrocarbon groups promoted positive feedback of pyrolysis in the oil. The free hydrogen produced by oil pyrolysis increased the acidity of the oil, which in turn increased the solubility of the water produced by sheath depolymerization. The chain depolymerization of TPEE was more severe than that of PTFE, further exacerbating the deterioration of TPEE-containing oil.
The poly-m-phenyleneisophthalamide (PMIA) is widely used in the electrical field due to its numerous favorable characteristics, but its poor thermal conductivity limits its application. In this study, PMIA was modified with nano-silica (SiO2) to improve its thermal and mechanical properties. Using iso-phthalic acid and m-phenylenediamine as monomers, the changes in the thermodynamic properties and microstructure parameters of SiO2-modified PMIA were analyzed using molecular dynamics before and after modification in the temperature range of 250~450 K. It was found that adding SiO2 improves the Young’s modulus and Shear modulus of PMIA, and the mechanical properties of PMIA, and SiO2/PMIA composites deteriorate with increasing temperature, but the mechanical properties of SiO2/PMIA composites are always better than those of pure PMIA in the temperature range of electrical equipment. Meanwhile, after doping SiO2 with the radius of 8 Å, the glass transition temperature of PMIA increases by 27.11 K, and its thermal conductivity increases from 0.249 W m−1 K−1 to 0.396 W m−1 K−1. When SiO2 is added to PMIA, the thermal expansion coefficient of PMIA will decrease in both glass and rubber states, and its thermal stability will improve. In terms of microstructure parameters, the free volume distribution of the SiO2/PMIA model is less easily dispersed than that of the PMIA model, indicating that the addition of SiO2 can improve the related properties of PMIA by hindering the movement of molecular chains.
The temperature distribution and deformation of the transformer windings cannot be measured in a distributed manner by the traditional method and failure location cannot be performed. To solve these problems, we present a transformer winding temperature and strain based on a distributed optical fibre sensing detection method. The design of the optical fibre winding composite model is developed and simulated winding temperature rise test and local deformation test distinguish between measuring the winding temperature and the strain curve. The test results show that the distributed optical fibre can transmit wire strain efficiently. Optical fibres, in the process of winding, have a certain pre-stress. Using the Brillouin–Raman joint measuring method, one can effectively extract the optical fibre temperature and strain information and measure the length of the winding direction of the temperature and strain distribution curve to a temperature measurement precision of ±2 °C and strain detection accuracy of ±50 με. The system can carry out local hot spot and deformation localisation, providing new ideas for the transformer winding state monitoring technology.
Winding overheating is a common fault in a transformer. To detect the temperature, the most widely used method is a point-type measurement, but traditional measurement methods cannot obtain the whole temperature distribution in a transformer. Taking this into consideration, a new method with which to measure the temperature of transformer windings was proposed. Based on Raman scattering, a new fibre-optic composite winding model was developed. The feasibility of the model was verified by electrical as well as temperature, field simulation and power frequency resistance testing. To assess the practicality and accuracy of the new model, a distributed optical fibre temperature measurement platform was built, and a series of experiments were designed. According to the data collected, the temperature measurement error based on the method could be limited to 1 °C while the positioning accuracy error was within 1 m, which meant that the new approach can satisfy the requirements of transformer winding temperature measurement and locate hot spots in the winding.
To accurately detect and monitor the internal temperature of an operating power transformer, the distributed optical fiber sensor (DOFS) was creatively applied inside an oil-immersed 35 kV transformer through high integration with the winding wire. On the former basis, the power transformer prototype with a completely global internal temperature sensing capability was successfully developed and it was also qualified for power grid operation through the ex-factory type tests. The internal spatially continuous temperature distribution of the operating transformer was then revealed through a heat-run test and the numerical simulation was also applied for further analysis. Hotspots of windings were continuously located and monitored (emerging at about 89%/90% height of low/high voltage winding), which were furtherly compared with the IEC calculation results. This new nondestructive internal sensing method shows a broad application prospect in the electrical equipment field. Also, the revelation of transformer internal distributed temperature can offer a solid reference for both researchers and field operation staff.