This paper presents an investigation into the effect of dissolved gases (DGs) on the insulating properties, such as breakdown strength, of Midel EN 1204 natural ester oil and Poweroil TO 1020 60U mineral oils. The gasses were generated by simulating thermal fault/s at 130 °C, 210 °C, 340 °C, 400 °C, and 450 °C. Dissolved gas analysis (DGA) was conducted according to IEC 60567 to determine the concentrations of H2, CH4, C2H6, C2H4, C2H2, and CO in each of the twelve oil samples. Moisture was measured using the Karl Fischer Method according to IEC 60814. The breakdown voltage (BDV) was measured according to IEC 60156. The results show that total dissolved gas concentration and rate of rise increased with fault temperature in both oils. For this relatively short time experiment, the rise in concentration of DGs had minimal effect. The overall BDV 73.7 kV (virgin ester oil BDV) increased to 76.3 kV at 450 °C for natural ester oil, whereas the BDV of mineral oil decreased from 68.7 kV to 63.1 kV. These findings showed that natural ester oil has better insulation stability under thermal stress.
Understanding how geometry, surface condition, and polarity influence surface flashover is important for improving the reliability of polymeric insulation in high-voltage systems exposed to transient overvoltages. The purpose of this study was to experimentally investigate visible arc path behaviour on polymeric insulators made of polymethyl methacrylate (PMMA), polyvinyl chloride (PVC), and nylon under standard 1.2/50 µs lightning voltage impulses. Cylindrical, concave, and convex profiles were tested in a rod–plane configuration for both positive and negative polarities under clean and sunflower oil- coated surface conditions. Seven arc types were observed. While the visible arc path was governed mainly by geometry and polarity, the electrical breakdown response exhibited material-dependent effects. Positive-polarity oil-coated samples generally exhibited longer time-to-breakdown, while negative-polarity tests produced higher breakdown voltages, and oil often reduced the withstand level. The large variability in time-to-breakdown data indicates that impulse flashover is strongly stochastic and sensitive to small surface or field variations. The findings highlight the need for improving control of surface films, expanding environmental testing, and conducting further modelling to predict flashover behaviour across different insulator designs.
High-voltage cable joints are critical components where electric stress concentration often leads to insulation failure. This study evaluated three materials to find optimal configurations for controlling stress in 33 kV applications: PVC tape, stress-grading mastic, and semiconductive rubber tape, with initial relative permittivities of 2.96, 2.66, and 5.07, respectively. Dielectric measurements using a Schering Bridge at voltages of up to 3700 V determined material properties and breakdown characteristics. Semiconductive rubber withstood the highest voltage of 3700 V, while mastic failed at 1350 V. Finite element simulations showed that baseline configurations without proper insulation had a peak stress of 4.3 kV/mm. Simulations of individual materials identified non-linear resistive compounds, such as ZnO-based materials and carbon-black-filled polymers, as the most effective for stress control at conductor interfaces. A three-layer graded design, arranging materials by decreasing permittivity from the conductor outward, reduced the peak stress by 33% to 2.9 kV/mm. These results demonstrate that strategic permittivity grading combined with appropriate material selection ensures uniform field distribution and improved reliability in HV cable joints.